1. Introduction
According to statistics from the National Fire Data System of the National Fire Agency[1], a total of 37,613 fires occurred in 2024, with 28.09% (10,566 cases) attributed to electrical factors. This made electrical causes the second leading factor after negligence, which accounted for 44.98% (16,917 cases). A detailed analysis of fires caused by electrical factors reveals that the most common cause was unconfirmed short circuits (32.76%, 3,461 cases), followed by short circuits due to insulation deterioration (18.19%, 1,922 cases), tracking-induced short circuits (13.02%, 1,376 cases), contact failure-related short circuits (11.75%, 1,242 cases), overload/overcurrent (7.72%, 816 cases), other causes (7.69%, 812 cases), compressive damage-induced short circuits (3.72%, 393 cases), earth leakage/ground faults (2.56%, 270 cases), partial disconnections (1.57%, 166 cases), and layer short circuits (1.02%, 108 cases). Overall, short circuits accounted for 80.46% of fires caused by electrical factors. Short circuits are a primary cause of arc faults, which increase the risk of fire due to continuous electrical discharges and high-temperature sparks.
Several large-scale fires in Korea have been attributed to electrical arcs, including the Jecheon Sports Center fire in 2017, the Miryang Sejong Hospital fire in 2018, the Cheonan Ramada Hotel fire in 2019, the Icheon Coupang Logistics Center fire in 2021, and both the Seocheon Special Market fire and the Bucheon hotel fire in 2024. Given that arc faults are a leading cause of electrical fires, the demand for arc-fault circuit interrupters (AFCIs) has been increasing. These devices are designed to automatically detect arc faults and cut off power to prevent potential hazards. In many countries, AFCI installation has been mandated to reduce the risk of electrical fires. In the United States, the importance of AFCIs was first recognized in 1999, leading to the establishment of the UL 1699 standard for arc-fault circuit interrupters. In 2002, the National Electrical Code (NEC), which sets standards for electrical installations, mandated AFCI installation in residential buildings, contributing to an approximately 65% reduction in electrical fires in homes. Subsequently, the international standard IEC 62606 for arc-fault detection devices (AFDD) was introduced in 2013. Beginning with Germany in 2018, testing and installation standards were developed across Europe, including in the United Kingdom, Austria, and France, leading to the widespread adoption of AFCIs[2].
In Korea, electrical installation safety standards mandate the use of molded case circuit breakers (MCCBs) and earth-leakage circuit breakers (ELCBs). Specifically, MCCBs serve as main breakers to protect against overloads and short circuits, while ELCBs function as branch breakers to prevent earth leakage, overloads, and short circuits. ELCBs are primarily employed in Korea to prevent electrical fires and electric shock incidents. However, in the United States and Canada, AFCIs are widely used to mitigate electrical fire risks, while ELCBs are primarily utilized for protection against electric shock accidents.
In response to the growing risk of electrical fires in Korea, certification standards for arc alarming devices were introduced in 2002, and the installation of AFDDs was recommended in 2016 through national construction regulations. However, their effectiveness has been limited due to the lack of mandatory installation requirements. In 2021, the Korea Electro-Technical Code (KEC) 214.2 stated that "devices conforming to KS C IEC 62606 (General Conditions for AFDD, AFCI) may be installed in branch circuits of 20 A or less that have a high fire risk, in order to reduce the risk of fires caused by electrical arcs." Additionally, the National Fire Agency included further recommendations for AFCI installation in its Construction Committee Review Standard Guidelines[3]. Following major fire incidents at the Coupang Logistics Center and Seocheon Market, the Ministry of Trade, Industry, and Energy has advocated for the mandatory installation of AFCIs in fire-prone facilities, such as traditional markets and logistics centers, in accordance with the KS C IEC 62606 standard. However, the effectiveness of this measure remains limited since installation is only recommended rather than required by law. To justify the necessity of AFCI implementation, further research is needed to assess the operational limitations of ELCBs, which have traditionally been used as branch circuit breakers, particularly in detecting low-current series arcs. Previous research on ELCBs in Korea has primarily focused on the tracking characteristics of ELCB insulation materials[4,5], operational behavior under overcurrent conditions[6], operational range under short-circuit currents[7], and performance under surge voltage[8]. These studies have emphasized insulation properties, overcurrent response, short-circuit conditions, and high-voltage scenarios.
Against this backdrop, the present study aims to analyze the operational characteristics of ELCBs in response to low-current series arcs to determine the necessity of AFCIs by identifying the operational limitations of conventional ELCBs. Five commercially available ELCBs, each rated for 20 A, were selected as experimental specimens. Their operational characteristics were analyzed under series arc conditions using a series arc circuit constructed with HFIX wires. The experiment was conducted with load currents of 5 A, 10 A, 15 A, and 20 A, representing normal operating conditions, as well as 30 A, representing an overcurrent scenario.
2. Experiment
2.1 Experimental specimens
Figure 1 presents the experimental specimens used in the study, which consisted of ELCBs obtained from five manufacturers: A, B, C, D, and E. All ELCBs featured a rated sensitivity current of 30 mA, a rated breaking current of 2.5 kA, an AC rated voltage of 220 V, and a rated current of 20 A.
2.2. Experimental method
To identify data representing the highest risk, each experiment was conducted at least five times under controlled environmental conditions: a room temperature of 22 ± 5 °C and a humidity of 50 ± 5%. Figure 2 illustrates the experimental setup. To examine the operational characteristics of ELCBs under low-current series arcs, a wire connected to the secondary terminal of the test specimen ELCB was fixed at 6.7 cm using an HFIX 2.5 SQ wire. Meanwhile, a wire connecting the terminal block (TB) to a vibration tester was set at 3.2 cm to simulate a short-circuit condition. To generate series arcs, accidental short-circuit conditions were replicated by removing 0.5 cm of the sheath from the contacting parts, ensuring direct copper conductor contact. The conductors were then overlapped and separated by 0.2 cm. Vibration was applied to induce a consistent series arc caused by contact failure. To apply vibration, the vibration tester shown in Figure 3(a) was used, operating at 850 rpm determined to be the optimal setting for arc generation based on preliminary tests. Currents of 5 A, 10 A, 15 A, and 20 A, within the normal operating range of ELCBs, were applied using the AC load tester shown in Figure 3(b). Additionally, to examine operational characteristics under overload conditions, a 30 A current 1.5 times the rated current (20 A) was applied. To assess the fire risk associated with series arcs and the securing of ELCB wires, grooves were created in a plasterboard to hold the wires in place. Furthermore, 0.1 g of sawdust was added to evaluate the potential fire hazard posed by low-current series arcs. The shoulder waveform generated during series arc occurrences was observed by measuring voltage and current with an oscilloscope (Wavesurfer 64Xs-A, Lecroy Co., USA). Additionally, the thermal properties of the contact points where series arcs occurred were recorded every 5 s using a thermal imaging camera (Testo 890, Testo Co., Germany). The experiment lasted for 300 s to ensure the stability of the AC load tester. For safety reasons, the ELCBs were manually stopped if sawdust ignition was observed or if the ELCBs activated during testing.
3. Experimental Results and Discussion
All experimental results were compared to the normal state (i.e., without short circuits or sheath damage) to assess the risks associated with series arc occurrences.
3.1 Load current of 5 A
Figure 4 presents the experimental results for a load current of 5 A. In the normal state, the wire temperature exhibited minimal variation, increasing by only 0.6 to 1.1 °C compared to the initial temperature. In contrast, during the series arc-fault state, the temperature rose significantly, increasing by a minimum of 81.4 °C and a maximum of 96.4 °C from the initial value, reaching a peak of 117.6 °C within 300 s. No ignition of the sawdust was observed. The ELCBs did not activate, as the current in both the normal and series arc-fault states remained below the rated current of the ELCBs.
3.2 Load current of 10 A
Figure 5 presents the experimental results for a load current of 10 A. In the normal state, the wire temperature showed minor fluctuations, increasing by 2.1 to 2.8 °C compared to the initial temperature. However, in the series arc-fault state, the temperature increased drastically, rising by at least 314.1 °C and at most 334.8 °C from the initial value, reaching a peak of 358.0 °C within 300 s. Although this temperature exceeded the ignition threshold of sawdust, no ignition occurred. As series arcs are influenced by load currents, the thermal imaging camera detected high temperatures during arc generation. However, due to the low arc energy and a slight current reduction caused by arc resistance (Rarc) at the contact points, ignition did not occur. The ELCBs did not activate, as the current remained below the rated value in both the normal and series arc-fault states.
3.3 Load current of 15 A
Figure 6 presents the experimental results for a load current of 15 A. In the normal state, the wire temperature increased by 4.0 to 4.3 °C from the initial value, a slightly higher rise than observed with a 10 A load current, though no fire risk was identified. Conversely, in the series arc-fault state, the temperature rose sharply, increasing by a minimum of 307.8 °C and a maximum of 337.0 °C and reaching a peak of 357.1 °C, which indicates a potential fire hazard. The rate of temperature increase was higher than in the 10 A case, as arc energy grew with increasing arc current. Sawdust ignition occurred between 135 and 150 s. However, the ELCBs did not activate, as the current remained below their rated value. Additionally, due to memory limitations, the thermal imaging camera captured temperature data as images every 5 s rather than as continuous video. The temperature range was set between 0 and 350 °C to more accurately monitor the initial temperature rise. While the recorded temperatures reflect conditions just before ignition, the actual temperature at the moment of flame formation was likely higher.
3.4 Load current of 20 A
Figure 7 presents the experimental results for a load current of 20 A. In the normal state, the wire temperature increased slightly, rising by 12.4 to 13.0 °C compared to the initial temperature, with no fire risk identified. However, in the series arc-fault state, the temperature increased significantly, rising by at least 235.8 °C and up to 294.9 °C from the initial value, reaching a peak of 316.8 °C. At this point, sawdust ignition was observed, indicating a fire hazard. The temperature increased 4.2 times more rapidly than in the 15 A case, as arc energy further escalated with higher arc current. Sawdust ignition occurred between 30 and 35 s. However, the ELCBs did not activate, as the current remained below their rated value in both states.
3.5 Load current of 30 A
Figure 8 presents the experimental results for a load current of 30 A. When overcurrent was applied, exceeding the ELCB's rated current, the wire temperature fluctuated between 24.6 °C and 41.4 °C above the initial value, reaching a peak of 65 °C under normal conditions. This temperature remains below the allowable limit of 90 °C for HFIX wires, indicating no fire risk in the wires. The ELCBs from companies A, B, and D tripped between 60 and 180 s upon detecting overcurrent, while those from companies C and E remained unaffected throughout the experiment. The lack of response from the latter ELCBs is likely due to discrepancies with the manufacturer's operating characteristic curve. In the series arc-fault state, the temperature increased significantly, rising by at least 261.5 °C and up to 297.8 °C from the initial value, reaching a peak of 321.7 °C. At this point, sawdust ignition occurred, indicating a fire risk. The rate of temperature increase was twice as high as in the 20 A case, as arc energy further escalated with the growing arc current. Sawdust ignited between 15 and 25 s. However, the ELCBs in the experimental setup did not trip before ignition occurred. For safety reasons, the ELCBs were manually turned off once the sawdust caught fire to conclude the experiment. Consequently, it was not possible to confirm whether the ELCBs would have eventually activated after ignition. If the conditions were similar to the normal state or if the current decreased slightly due to arc resistance (Rarc) at the contact point, the ELCBs might have been triggered with a slight delay.
Figure 9 presents oscilloscope waveforms for both the normal and series arc-fault states when load currents of 15 A and 20 A were applied, where the fire risk increased within the ELCB's rated current range. When a load current of 15 A was applied, the RMS value was recorded as 13.58 A in the normal state and 10.53 A in the series arc-fault state. For a load current of 20 A, the RMS value was measured at 22.43 A in the normal state and 18.19 A in the series arc-fault state. In the series arc-fault state, arc current is generated based on the load current, but it tends to decrease slightly due to the arc resistance present at the contact points. Furthermore, the shoulder phenomenon, which is characteristic of series arcs, was also observed.
Figure 10 displays images of the ELCBs in operation. Figure 10(a) shows an ELCB tripping in the normal state when an overcurrent of 30 A was applied. As shown in Figures 10(b) and 10(c), sawdust did not ignite even when a series arc occurred at currents between 5 and 10 A. In contrast, as shown in Figures 10(d) through 10(f), sawdust ignited due to a series arc at currents between 15 and 30 A, yet the ELCB did not trip. Specifically, at currents between 15 and 20 A below the ELCB’s rated threshold sawdust ignited, leading to a fire, but the ELCB failed to detect the abnormal state and did not activate. This suggests that series arcs occurring within the rated current range cannot be effectively detected or mitigated, even with ELCBs installed.
4. Conclusions
Based on the study’s results, the following conclusions can be drawn regarding the operational characteristics of ELCBs in relation to low-current series arcs:
1. In the normal state, when the load current remained below the ELCB’s rated 20 A, the maximum temperature increase ranged from 12.4 °C to 13.0 °C above the initial temperature, indicating no fire risk. Additionally, the ELCBs did not activate since the load remained below their rated current. When an overcurrent of 30 A 1.5 times the rated current was applied, the temperature increased between 24.6 °C and 41.4 °C above the initial value, with a peak temperature of 65 °C. However, this remained below the allowable limit of 90 °C for HFIX wires, still indicating no fire risk. Moreover, the ELCBs from companies A, B, and D tripped between 60 and 80 s after detecting the overcurrent, whereas those from companies C and E did not activate.
2. Under series arc-fault conditions at 15 A and 20 A both below the ELCB's rated current a rapid temperature increase exceeding 300 °C occurred due to arc energy. Sawdust ignited within 135-150 s and 30-35 s, respectively, indicating a significant fire risk. However, the ELCBs did not activate since the load remained below their rated current. When an overcurrent of 30 A 1.5 times the rated current was applied, the maximum temperature reached 321.7 °C, and sawdust ignited within 15-20 s due to the rapid increase in arc energy. Despite the high fire risk, the ELCBs did not activate during the experiment, even though they had tripped under normal conditions. Notably, for safety reasons, the ELCBs were manually shut down immediately after ignition, making it impossible to confirm whether they would have eventually activated. However, it was verified that ignition occurred before any tripping of the ELCBs.
These experimental results confirm that the ELCBs currently used in Korea for preventing electrical fires and shock accidents have limitations in tripping, even when fires occur due to series arcs within the rated current range. Therefore, as practiced in other countries, the implementation of AFCIs is considered essential to mitigate the fire risk associated with series arcs. However, AFCIs must undergo extensive verification processes before being introduced into real-world applications to ensure their effectiveness and minimize financial burdens. Since electrical fires can occur under various conditions, it is crucial to verify AFCI performance under diverse environmental scenarios beyond standard tests such as UL 1699, as demonstrated in this study. Future research will assess the effectiveness of AFCIs through experiments involving electrical fire generation with AFCI protection.