2.1 GSLE and smoke detection experimental method
2.2 FDS simulation method
3. Experimental and Computational Results and Discussion
3.1 GSLE results
3.2 Comparison between the smoke detection results from the compartment experimental device and the FDS smoke detection model
4. Conclusions
The FDS results calculated by inputting the experimental smoke particle mass-specific light extinction coefficient were in good agreement with the OPM changes measured during the smoke detection experiment results. When it was assumed that the smoke detector transmitted a fire alarm signal at an OPM of 3.28%/m, it was found that the smoke detection times agreed relatively well at 175 seconds and 179 seconds, respectively.
When the experimental results were compared to the smoke detection times that were calculated by inputting the default mass-specific light extinction coefficient (8,700 m2/kg) in the FDS smoke detection model and the relatively low mass-specific light extinction coefficient (4,500 m2/kg) of PVC, delay times of 27 seconds and 125 seconds, respectively were observed.
Based on the experiments and the FDS simulation results, it was possible to confirm that the optical properties of the smoke particles can significantly affect fire detection times. Therefore, the optical properties of smoke particles emitted by combustible fuels in compartments must be considered when setting the OPM values of smoke detectors.