Int J Fire Sci Eng > Volume 36(4); 2022 > Article
Hong and Park: Effects of Optical Properties of Smoke Particles on Fire Detection Characteristics predicted by a Fire Dynamic Simulator Model

Abstract

This study examined the smoke detection time prediction performance of the Fire Dynamics Simulator (FDS) in relation to the optical properties of smoke particles. Specifically, this work explored how smoke detection times are affected by the mass-specific light extinction coefficient, an input value needed to predict FDS smoke detection times. Therefore, a smoke generator and a smoke detection sensor that employs the light extinction principle were installed in a fire compartment, with the mass-specific light extinction coefficients of the smoke particles generated by the smoke generator measured through Gravimetric Sampling and Light Extinction (GSLE) experiments. FDS fire simulations were performed under the same conditions as the smoke detection experiments to compare the Optical Per Meter (OPM) of the detector. The results confirmed that the FDS fire simulation was consistent with the smoke detection experiments when the measured mass-specific light extinction coefficient of the smoke particles was entered as input. In addition, it was found that fluctuations in the mass-specific light extinction coefficient, an optical property of smoke particles, may significantly affect smoke detection times by directly affecting the OPM.

1. Introduction

Currently, performance-based fire protection design (PBD) is used to minimize the human and property damage caused by structural fires and to evaluate the fire stability of structures from an engineering perspective[1]. PBD helps to optimally implement fire safety by designing fire protection facilities that are appropriate for the characteristics of the target building using the most recently developed fire protection engineering technology[2]. In short, PBD is an engineering design method that ensures the fire robustness of buildings to ensure facilities installed based on PBD can guarantee sufficient egress time to protect human life when fires occur. To maintain their robustness, buildings are designed by comparing the available safe egress time (ASET), calculated from the time of ignition to the time when occupants can no longer take action to escape to a safe place, and the required safe egress time (RSET), the time taken for the occupants to escape to a safe place from the place where they were at the time of ignition[3,4,5]. In Korean PBD, fire simulations are the main method used to evaluate time-related factors (ASET and RSET) for the safety of people during fires. In particular, the open-source Fire Dynamics Simulator (FDS), developed by the National Institute of Standards and Technology, United States (NIST), is mainly used[6,7,8].
Through fire simulations, researchers examine the time distributions of physical properties and chemical species related to various risk factors such as heat, smoke, and toxic gas, that prevent occupants from evacuating to a safe place by determining how quickly these factors worsen. In particular, predicting the distribution of smoke concentration within a specific space when a fire occurs is crucial for safe evacuation and human safety. However, qualitative research on the smoke detection parameters needed to aid in the rapid evacuation of people in FDS fire predictions has been insufficient. In methods such as FDS fire simulations, which generate fire alarm signals by detecting the degree of light extinction caused by smoke particles, prediction characteristics can vary according to the optical properties of the smoke particles[7].
In general, among the optical properties of smoke particles employed in FDS fire simulations, a default value (8,700 m2/kg)[9] is used as the mass-specific extinction coefficient. However, the mass-specific extinction coefficient can vary according to the combustibles and combustion conditions inside the fire compartment[10], which can significantly affect the fire alarm signal of the smoke detector. Therefore, this study examined the detection properties of the FDS smoke detection model according to the optical properties of particles that are directly related to smoke detection.

2. Experimental and Computational Methods

2.1 GSLE and smoke detection experimental method

To perform the smoke detection experiment’s FDS simulation, an accurate smoke particle mass-specific light extinction coefficient is needed as input. Therefore, the smoke particles generated by the smoke generator used in the experiments were made to flow into the GSLE experimental device shown in Figure 1 to measure the mass-specific light extinction coefficient. For specific descriptions of the GSLE device and methods, consult the reference literature[10]. As shown in the figure, the smoke particles generated by the smoke generator were mixed with air and made to flow into the transmission cell (TC). The TC was fabricated from aluminum in a 0.8 m × 0.08 m × 0.08 mm cuboid shape. The interior was painted with matte black paint to prevent the reflection and scattering of light by the interior surfaces. The smoke particles flowed into the TC and were exposed to a laser light source (633 nm) that passed through optical windows installed at both ends of the TC. Optical windows (BK7 window with an anti-reflection coating) with a diameter of 8 mm were installed at both ends of the TC so that the laser light could pass through. At this time, the intensity of the laser light with a 633 nm wavelength was reduced by the light absorption and scattering of the smoke particles. A photodetector was installed to measure the reduced intensity of the incident light. In addition, a band heater was installed at the bottom of the TC to prevent smoke particles from being deposited through the thermophoresis effect.
A vacuum pump was installed on the downstream side of the TC to create a pressure difference between the upstream inlet and the downstream outlet so that the smoke particles that were mixed with air could flow into the interior of the TC. In addition, a smoke particle collection device was installed at the downstream end. The collection device was equipped with a glass fiber filter with pores of 0.7 μm and designed to extract only smoke particles from the flow of smoke particles mixed with air. A mass flow meter (MFC) was installed on the rear end of the filter to compensate for the pressure difference between the filter ends that can occur due to the accumulation of smoke particles.
Figure 2 shows the experimental compartment device for performing the smoke detection experiments. As can be seen in the figure, it was fabricated with a size of 2.4 (W) × 2.6 (H) × 5.9 (L) m. It was designed so that the air was supplied from the top duct flow (1.1 m/s), circulated in the interior, and recovered via the bottom duct. Through this process, temperature and humidity adjustments were made, and the air was purified. Also, the forced ventilation flow velocity was generated via the recirculation process. In addition, a smoke detector that operated on the light extinction principle was installed on the front of the bottom duct, which was the part where the smoke flowed in, to make it easy to detect smoke particles. The smoke generation fuel was placed at the right end near the inlet, and a load cell was installed to measure the precise reduction in the mass of the smoke generation fuel. Also, to observe the behavior of the smoke generated by the smoke generation fuel, four cameras were installed at the locations shown in the figure to monitor the experiment process.

2.2 FDS simulation method

To examine the detection properties of the FDS smoke detection model according to the optical properties of the particles in the smoke detection experiments, this study used FDS (Ver. 6.7.9), which is capable of performing large eddy simulation (LES). In LES, the instantaneous flow variable is divided into a Grid Scale (GS) component (f̃) and a Sub-Grid Scale (SGS) component (f″). Here, the GS component is determined by the Farve filter ( f˜=ρf¯ρ¯), and the 'over-bar' mark refers to a spatial filter. As a result, the Navier-Stoke equation, which uses a low Mach Number (MA < 0.3) approach, is expressed as the following LES equation[11]:
(1)
∂ ρ¯∂ t=∇•(ρ¯u¯)=0
(2)
∂ ρ¯u¯∂ t=∇•(ρ¯u¯u˜)=-∇ρ¯-∇•(τ¯+τsgs)+ρ¯g
(3)
∂ ρ¯ Y˜i∂ t=∇•(ρ¯ Y˜iu˜)=∇•(ρ¯D˜i∇ Y˜i+Jsgs)+m˙¯i″ ′
(4)
∂ ρ¯h˜∂ t=∇•(ρ¯ h˜u˜)=D˜p0D˜t+∇•(k˜ ∇ T˜+∑iρ¯D˜ih˜i ∇ Y˜i+qsgs)-∇•qr¯
(5)
ρ¯=p0W¯R T˜
τsgs, J sgs, and qsgs, which occur in the spatial filter process, refer to the stress tensor, chemical species, and thermal flux, respectively and represent the SGS component effect. In the above equations, additional modeling is performed for closure. To model the SGS terms, information on characteristic length and time scale is required. To do so, the length scale is set as the grid size, i.e. Δ̄= (ΔxΔyΔz)1/3, and the time scale is determined by the original Smagorinsky model[12], which assumes an equilibrium between energy generation and extinction in SGS.
Figure 3 shows the inside of the experimental compartment device used in the FDS fire simulation modeling, and a 3.75 (L) × 2.2 (W) × 2.2 (H) m space was modeled as 145,200 grid units in the same way as the experimental device. The analysis boundary conditions were set so that the mass-specific light extinction coefficient, obtained through the previous GSLE experiments, and an airflow of 1.1 m/s at the top duct (inlet) was entered as input, and the air was returned through the bottom duct (outlet). Here, the mass reduction rate obtained from the load cell was converted to the smoke generation rate, and the smoke generation rate was analyzed in the same way as in the experiments. Also, to compare the FDS smoke detection model’s response properties with the optical properties of the smoke particles, the default value of mass-specific light extinction coefficient (8,700 m2/kg) used in FDS and the value of PVC (4,500 m2/kg), which is known to have a relatively low mass-specific light extinction coefficient, were entered as input, and additional comparison and analysis were performed.
Figure 4 illustrates the operational concept of the photoelectric smoke detector used in the FDS model. This approach detects changes in the incident light intensity due to generated smoke particles and generates a fire signal if the OPM set in the smoke detector is reached. OPM (Optical Per Meter) can be calculated through changes in the installed smoke detector’s Cs over time[13]:
(6)
OPM={1-exp(Cs(t))}×100={1-exp{-Kmρsootysoot(t)}×100 %
Here, ρsootysoot is the density of the smoke particles, and the optical properties of the smoke particles are calculated through the mass-specific light extinction coefficient. Since the detector is affected by its internal shape and flow, the following equation, which was proposed by Cleary, is used to calculate the reactions and latency that can occur due to the shape and internal flow[14].
(7)
te=αeuβe   ;         tc=αcuβc   ,         Δ t=te+tc
In the equation above, te is the time when the smoke particles flow into the detector; tc is the time when the smoke particles are mixed within the detector; Δt is the detector’s response delay time; u is the movement speed of the particles; α and β are empirical constants for considering the inflow and mixture of the particles, respectively. In this study, the smoke detector was exposed to the outside; therefore, the detector’s response delay time was set as 0 to perform the FDS fire simulations.

3. Experimental and Computational Results and Discussion

3.1 GSLE results

Figure 5 shows the light transmittance (I/Io) over time obtained through GSLE experiments. The incident intensity Io is the intensity of the light source in the presence of air without smoke particles, and I is the light intensity in the presence of air mixed with smoke particles. A photodetector was used to measure both I and Io. As shown in the figure, the light transmittance was relatively constant before the air mixed with smoke particles flowed into the TC and after the supply was halted. Also, there were no changes in the light source size measured in the smoke particle collection section (using a photodetector parallel to the laser); therefore, it can be said that the stability of the light source was ensured. The light transmittance rapidly decreased as soon as the air mixed with smoke particles began to flow into the TC, and it soon arrived at a quasi-steady state. At this time, a photodetector was used to measure the incident intensity of the light source before the air mixed with smoke particles flowed into the TC and then measured the lowered intensity of the light source when the air mixed with smoke particles passed through the TC. Thus it was possible to find the calculated transmittance over time.
To measure the mass-specific light extinction coefficient, the method employed in this study performed an inverse calculation based on the correlation between the concentration of smoke particles measured by the optical method (Cs) and the collected concentration of smoke particles (fvg). The calculation was performed as shown below according to the Beer-Lambert law[15]:
(8)
Cs=-1Lln(IIo)
(9)
fvg=msVtρsoot
(10)
Km=Cs Vtms=-Vt(lnII0)Lms
Here, Cs (commonly referred to as the smoke optical density) is the light extinction per unit length caused by smoke particles; ms is the measured mass of the smoke particles collected by the filter; V is the volumetric flow rate, including the smoke particles; t is the sampling time of the particle; L is the laser’s path length. For ms, the mass of the smoke particles collected by filtering for approximately 30 seconds of collection time was measured using a precision balance. ρsoot is the density of the smoke particles, and this study used a soot particle density value (1.74 g/cm3) widely used irrespective of the fuel[16]. These values were used to find the mass-specific extinction coefficient through 5 rounds of experiments, as shown in Table 1.
To calculate the smoke yield that was inputted into FDS, the mass reduction rate was measured using the loadcell that was installed in the compartment, and the results are shown in Figure 6. The smoke yield that was calculated from the measured smoke generator mass reduction rate was used in the FDS to model the behavior properties of the smoke particles which occurred due to interaction with the airflow that was circulating in the compartment.

3.2 Comparison between the smoke detection results from the compartment experimental device and the FDS smoke detection model

Figure 7 shows the smoke detection experiment results from the experimental device and the analysis results in which the mass-specific light extinction coefficient (11,573 m2/kg) that was measured via the GSLE experiments was used in the FDS smoke detection model. It can be seen that smoke behavior over time agreed relatively well with the experimental results. In addition, it can be seen that the interior of the experimental device reached a uniform smoke concentration within around 60 seconds.
Figure 8 shows the results of comparing the OPM that was measured in real-time with the smoke detection experiments and the OPM that was predicted by the FDS smoke detection model by inputting the mass-specific light extinction coefficient obtained via the GSLE experiments. As shown in the figure, the OPM results of the smoke detection experiments and the FDS fire simulations agreed relatively well over time. In particular, the smoke particles were detected by the smoke detector starting at around 200 seconds, and the values rose rapidly.
Figure 9 shows changes in OPM over time, which were calculated by taking the mass-specific light extinction coefficient obtained via the GSLE experiments, the mass-specific light extinction coefficient that is used as the default value in the FDS smoke detection model, and PVC’s relatively low mass-specific light extinction. As shown in the figure, the changes in OPM over time appear the same in all three conditions; however, in comparison to the results that were calculated by inputting the mass-specific light extinction coefficient obtained via the GSLE experiments, it can be seen that the OPM values which were calculated in the other two conditions were relatively low. It was found that the results of performing the analysis by inputting the mass-specific light extinction coefficient of PVC differed by a factor of 2.5 or more from the results calculated by inputting the mass-specific light extinction coefficient obtained via the GSLE experiments. In addition, the results calculated by inputting the default value of mass-specific light extinction coefficient in FDS differed by a factor of around 1.2 at maximum. When engineers who were performing the analysis inputted the OPM value (3.28%/m) that is generally used in the FDS settings[17], the smoke detection time of 175 seconds measured in the smoke detection experiments agreed relatively well with the smoke detection time of 179 seconds that was calculated by inputting the mass-specific light extinction coefficient that was obtained via the GSLE experiments. However, a significant difference of 206 and 304 seconds was observed while inputting the default mass-specific light extinction coefficient and the mass-specific light extinction coefficient of PVC, respectively.

4. Conclusions

This study installed a photoelectric smoke detector in an experimental compartment device and performed smoke detection experiments. To compare the performance of the FDS smoke detection model, GSLE experiments were performed to measure the mass-specific light extinction coefficient, and FDS simulations were performed under the same conditions as the smoke detection experiments. In addition, the default mass-specific light extinction coefficient value used in the FDS smoke detection model and the relatively low mass-specific light extinction coefficient of PVC were used as input to compare the performance of the FDS smoke detection model, and the following conclusions were obtained.
  1. The FDS results calculated by inputting the experimental smoke particle mass-specific light extinction coefficient were in good agreement with the OPM changes measured during the smoke detection experiment results. When it was assumed that the smoke detector transmitted a fire alarm signal at an OPM of 3.28%/m, it was found that the smoke detection times agreed relatively well at 175 seconds and 179 seconds, respectively.

  2. When the experimental results were compared to the smoke detection times that were calculated by inputting the default mass-specific light extinction coefficient (8,700 m2/kg) in the FDS smoke detection model and the relatively low mass-specific light extinction coefficient (4,500 m2/kg) of PVC, delay times of 27 seconds and 125 seconds, respectively were observed.

  3. Based on the experiments and the FDS simulation results, it was possible to confirm that the optical properties of the smoke particles can significantly affect fire detection times. Therefore, the optical properties of smoke particles emitted by combustible fuels in compartments must be considered when setting the OPM values of smoke detectors.

Acknowledgments

This work is supported by the Korea Agency for Infrastructure Technology Advancement (KAIA) grant funded by the Ministry of Land, Infrastructure and Transport (Grant RS-2022-00156237).

Notes

Author Contributions

TK Hong.; formal analysis, investigation, and writing—original draft preparation, SH Park.; writing—review and editing. All authors have read and agreed to the published version of the manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

Figure 1
Schematic of experimental set-up for simultaneous GSLE measurement.
kifse-96827602f1.jpg
Figure 2
Schematic of smoke detection test compartment equipped with experimental devices.
kifse-96827602f2.jpg
Figure 3
FDS-modeled smoke detection test of experimental compartment device.
kifse-96827602f3.jpg
Figure 4
Light extinction process by soot particles in the smoke detector.
kifse-96827602f4.jpg
Figure 5
Light extinction over time obtained through the GSLE experiment.
kifse-96827602f5.jpg
Figure 6
Smoke production rate over time obtained through a loadcell measurement.
kifse-96827602f6.jpg
Figure 7
Comparisons of smoke spread behaviors in the compartment.
kifse-96827602f7.jpg
Figure 8
Comparison of OPM calculated for FDS result and smoke detection test of compartment experimental device test result.
kifse-96827602f8.jpg
Figure 9
Comparison of OPM calculated for FDS results (Smoke-generating fuel, PVC and FDS default).
kifse-96827602f9.jpg
Table 1
Mass-Specific Extinction Coefficient Obtained through GSLE Experiment
Mass-specific Extinction Coefficient, Km (m2/kg)
Test 1 11,671
Test 2 12,113
Test 3 10,174
Test 4 11,553
Test 5 12,352
Average 11,573

References

1. V. R. Beck, “Performance-based fire engineering design and its application in Australia”, Fire Safety Science, Vol. 5, pp. 23-40 (1997), https://doi.org/10.3801/IAFSS.FSS.5-23 .
crossref
2. W. K. Kim, “Concept and design procedure of performance-oriented firefighting design”, Proceedings of 2005 Summer Annual Conference, Korean Institute of Fire Science & Engineering, pp. 5-21 (2005).

3. K. H. Kim, S. H. Lee, H. Y. Kim, T. H. Song and B. K. Jin, “Establishment of Building Fire Safety System Improvement of Building Fire Safety Regulations”, “KICT 2000-082”, Korea Institute of Construction Technology, pp. 31-37 (2000).

4. H. S. Han and C. H. Hwang, “Study on the Available Safe Egress Time (ASET) Considering the Input Parameters and Model Uncertainties in Fire Simulation”, Fire Science and Engineering, Vol. 33, No. 3, pp. 112-120 (2019), https://doi.org/10.7731/KIFSE.2019.33.3.112 .
crossref
5. H. S. Yun and C. H. Hwang, “Analysis of Prediction Results and Grid Size Dependence According to Changes in Fire Area”, Fire Science and Engineering, Vol. 33, No. 6, pp. 9-19 (2019), https://doi.org/10.7731/KIFSE.2019.33.6.009 .
crossref
6. H. Y. Jang and C. H. Hwang, “Obscuration Threshold Database Construction of Smoke Detectors for Various Combustibles”, Sensors, Vol. 20, No. 21, pp. 6272(2020), https://doi.org/10.3390/s20216272 .
crossref pmid pmc
7. H. S. Han, S. Y. Mun and C. H. Hwang, “Effects of User Dependence on the Prediction Results of Visibility in Fire Simulations”, Fire Science and Engineering, Vol. 35, No. 3, pp. 14-22 (2021), https://doi.org/10.7731/KIFSE.b5e493d9 .
crossref
8. J. H. McGuire and G. T. Tamura, “Simple Analysis of Smoke Flow Problems in High Rise Buildings”, Fire Technology, Vol. 11, pp. 15-22 (1975), https://doi.org/10.1007/BF02589997 .
crossref
9. K. McGrattan, R. McDermott, M. Vanella, S. Hostikka and J. Floyd, “Fire Dynamic Simulator Technical Reference Guide”, “NIST Special Publication 1018-1”, Sixth Edition., (2020).

10. T. K. Hong, B. S. Roh and S. H. Park, “Measurements of Optical Properties of Smoke Particulates Produced from Burning Polymers and Their Implications”, Energies, Vol. 13, No. 9, pp. 2299(2020), https://doi.org/10.3390/en13092299 .
crossref
11. J. W. Deardorff, “Numerical Investigation of Neutral and Unstable Planetary Boundary Layers”, Journal of Atmospheric Sciences, Vol. 29, No. 1, pp. 91-11 (1972), https://doi.org/10.1175/1520-0469(1972)029%3C0091:NIONAU%3E2.0.CO;2 .
crossref
12. J. Smagorinsky, “Gerneral Circulation Experiments with the Primitive Equations”, Monthly Weather Review, Vol. 91, No. 3, pp. 99-164 (1963), https://doi.org/10.1175/1520-0493(1963)091%3C0099:GCEWTP%3E2.3.CO;2 .
crossref
13. R. Friedman, “Risks and Issues in Fire Safety on the Space Station”, NASA Technical Memorandum 106430, (1994).

14. T. Cleary, A. Chernovsky, W. Grosshandler and M. Anderson, “Particulate Entry Lag in Spot-Type Smoke Detectors”, Fire Safety Science, Vol. 6, pp. 779-790 (1999).
crossref
15. D. F. Swinehart, “The Beer-Lambert Law”, Journal of Chemical Education, Vol. 39, No. 7, pp. 333-335 (1962), https://doi.org/10.1021/ed039p333 .
crossref
16. M. Y. Choi, G. W. Mulholland, A. Hamins and T. Kashiwagi, “Comparisons of the Soot Volume Fraction using Gravimetric and Light Extinction Techniques”, Combustion and Flame, Vol. 102, No. 1-2, pp. 161-169 (1995), https://doi.org/10.1016/0010-2180(94)00282-W .
crossref
17. X. Liu, D. Hou, J. Ji and H. Zhu, “Experiment and Numerical Simulation of Cable Trench Fire Detection”, Case Studies in Thermal Engineering, Vol. 28, pp. 101338(2021), https://doi.org/10.1016/j.csite.2021.101338 .
crossref


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next