Measurement of Smoke Entrainment Rate and Yield Ratio by a Downward Plume

Article information

Int J Fire Sci Eng. 2025;39(1):45-62
Publication date (electronic) : 2025 March 31
doi : https://doi.org/10.7731/KIFSE.2adca2ef
1New Constructor’s Network, 2-13-5 Nagata-cho, Chiyoda-ku, Tokyo, 100-0014, Japan
2Dept. of Architecture and Architectural Engineering, Kyoto University, C1-4 Kyotodaigaku Katsura, Nishikyo, Kyoto 615-8540, Japan
†Corresponding Author, TEL: +81-75-383-3273, E-Mail: harada@archi.kyoto-u.ac.jp
Presented at the 13th Asia-Oceania Symposium on Fire Science and Technology (Oct. 21-25, 2024, Daegu, Korea) & published in the Special Issue of the IJFSE.
Received 2025 February 27; Revised 2025 February 27; Accepted 2025 March 5.

Abstract

In some industrial buildings, ventilation system continues to be operated even after the break of fire in order to keep the necessary pressure differences. In such situations, supplied air at the ceiling creates a downward plume. The plume entrains smoke in the upper layer and move the smoke particles downward. As a result, lower air layer is contaminated by smoke. In this paper, model scale experiments were carried out to investigate the properties of downward plume. A smoke layer was created in the upper part of a model room. Fresh air was supplied downward via an outlet equipped at the ceiling. The velocity and temperature profiles and the mass flow rate of downward plume was measured by direct measurement method and gas analysis method. The mass flow rate was formulated by Zukoski’s plume formula and compared with experimental measurements. To evaluate the degree of contamination of the lower layer, the yield ratio of downward plume to lower layer was investigated with the Froude number at the bottom of smoke layer. The yield ratio was around 0.8.

1. Introduction

During the initial stage of fire, burning of the fire source is not so intense. Relatively low temperature smoke layer is generated beneath the room ceiling. During the period, heating, ventilation and air conditioning system (HVAC) may be still in operation. Fresh air is supplied from the outlet on the ceiling to downward as shown in Figure 1. Until fire is detected, and HVAC is stopped, air supply continues. As the supplied air goes through the smoke layer, air flow entrains the surrounding smoke. Then the air flow is contaminated by smoke and falls down to lower layer[1]. As a result, the lower air layer is contaminated and threat to the safe evacuation arises.

Figure 1.

Schematics of downward plume.

In some type of industrial buildings, such as nuclear facilities and/or clean rooms, the room is enclosed by air-tight walls and mechanically ventilated continuously to maintain the pressure of the room at a desired level, positive for clean rooms, negative for nuclear facilities. Even after the initiation of fire, the mechanical ventilation is continued in order to maintain the desired pressure level. In such cases, supplied air is mixed with smoke layer for a long period. In such situations, contamination of lower layer is a serious problem.

Concerning with the fire and smoke behavior in air-tight rooms with mechanical ventilation, research has been carried out by many authors. Audouin et al.[2] conducted a series of full-scale experiments in an air-tight compartment simulating oil spill fires and cable fires. Mechanical ventilation was equipped at the upper part of the compartment. Compartment size was 5.0 m × 6.0 m × 4.0 m (height). Fire was set at single compartment and at multiple compartments. While changing the heat release rates and mechanical ventilation rates, fire room pressure and flow rates of gases to adjacent compartments were measured. In the joint research among 9 electric companies in Japan[3], full-scale experiments were conducted in several compartments of volume 105 to 800 m3. Heat release rates and ventilation rates were varied. Fundamental data was acquired on temperatures and smoke concentrations. Based on the results, prediction formula of compartment temperature was developed. Prétrel et al.[4] carried out full scale experiments in a 400 m3 compartment with mechanical smoke exhaust and natural air supply. Compartment pressure, temperature, and heat loss to compartment boundary were measured and analyzed. However, flow behavior of smoke was not explicitly discussed.

Concerning with the basic characteristics of a plume, Morton[5] derived a set of closed form equations for an upward forced plume originating from a point source. Hino[6] extended the Morton’s method to a plume originating from a plane source of finite size. The assumptions applied by Morton and Hino are strict and the range of application of the equations was limited. Kubota[7] carried out an analysis of non-isothermal jet plume ejected vertically to a large space using the method proposed by Koestel[8]. Kofoed et al.[9] carried out full-scale experiments on displacement ventilation. The interaction between thermal plume and mechanical air flow was investigated. However, no discussions were made on the application to fire situations.

Ichikawa et al.[10] proposed a method to measure the air entrainment rate by a downward plume by model scale experiments. Plume mass flow rates were measured at the bottom edge of smoke layer. However, no measurements were made as to the mass flow rates of downward plume within a smoke layer, due to the difficulty in measuring the are velocities in the smoke layer. In this research, Ichikawa’s experimental method was improved to measure the velocity, temperature and mass flow rates within the smoke layer. The results are compared with existing prediction formulae and selected an appropriate formula. Algebraic formulas are proposed to calculate the mass flow rates and yield ratio to lower layer.

2. Experimental Methods

2.1 Experimental apparatus

To examine the characteristics of downward plume, model scale experiments were carried out. Schematics of experimental apparatus is shown in Figure 2. The apparatus consists of upper space and fire room separated by a ceiling board. The size of fire room is 1.8 (width) × 1.8 m (depth) × 1.2 m (height). Air is supplied to the upper space and flowed out downward via a square outlet (50 × 50 mm). To reduce the heat loss from the wall, ceiling and wall surfaces were insulated by ceramic fiber board of 25 mm thickness.

Figure 2.

Schematics of the experimental setup (unit: mm).

The fire room is equipped with a small gas burner simulating a fire source. The fuel supply rate was measured by a mass flow meter. The combustion gas formed a hot smoke layer beneath the ceiling. Air is supplied to an outlet equipped at the center of the ceiling. The supplied air forms a downward plume going through the smoke layer. The velocity and temperature profiles of the downward plume was measured in the measurement area covered by a traverse device. To keep the smoke layer to a steady state, excessive smoke was exhausted from the upper layer. CO2 concentrations were measured by a CO2 recorder (T&D, TR-76Ui) in upper smoke layer, lower air layer, air supply, smoke exhaust, zone close to gas burner and outside of the room.

The inner view of the fire room is shown in Figure 3. In the fire room, smoke is generated by a gas burner fired by natural gas. The height of gas burner was 630 mm above floor. Smoke was accumulated by the smoke reservoir first, then spread to whole area. The thickness and temperature of smoke layer were adjusted by changing the gas burner output and smoke exhaust rate. To measure the temperature and velocity profiles below the outlet, Pitot tube with a manometer (Okano, DP 1A), hot wire anemometer (Kanomax, air flow transducer, Model 6332) and type T thermocouples were equipped to a traverse device. Vertical temperature distribution was measured by a thermocouple tree (type T, 0.32 mm dia.). Half of the room surface was painted black in order to observe the flow patterns by using small white particles.

Figure 3.

Inner view of the fire room.

2.2 Experimental procedure

2.2.1 Schematics of procedure

The measurement was made by direct measurement method (DMM) and gas analysis method (GAM). DMM was applied to measure the mass flow rate of downward plume in the smoke layer. GAM was applied to measure the entrainment of smoke by the downward plume and yield of smoke to lower layer. The following is a procedure of measurements.

1) Activate the air supply and smoke exhaust fans and adjust flow rates to specific values.

2) Ignite the gas burner and adjust the heat release rate to a specific value.

3) Wait approximately 180 minutes until the smoke layer height and temperature profile are steady state.

4) At steady state, Pitot tube, hot wire anemometer and thermocouple are moved by the traverse device. Temperature and velocity profiles were measured on horizontal planes at every 50 mm up to 500 mm below the outlet. The results were used to obtain mass flow rate of plume by DMM.

5) After the DMM is finished, CO2 concentrations were measured at the positions shown in Figure 2. The values are used to calculate the entrainment of smoke by the downward plume and yield of smoke to lower layer by GAM[10]

6) Smoke layer height was determined either by Cooper’s N%-method[11] or by He’s integral ratio method[12]. In case of N%-method, N = 23% was used based on the observations by Ichikawa et al. for this specific arrangement[10].

2.2.2 Direct measurement method (DMM)

As shown in Figures 2, 3, Pitot tube and hot wire anemometers are equipped below the outlet. The sensors were put on a traverse device. At steady state, measurements were carried out by moving the sensors to appropriate positions. The measurement plane was set in the range of 0mm to 500mm below the ceiling at every 50mm as shown in Figure 4.

Figure 4.

measuring planes of direct measuring method (DMM).

Considering the sensitivity of sensors, Pitot tube value was adopted in the regions of plume axis where the velocity is relatively high. As the measuring point moves to peripherals of the plume, the velocity and temperature are reduced. In that region, the value by hot wire anemometer was adopted.

After measuring the horizontal distribution of vertical velocity and temperature, the mass flow rate was calculated by integrating the mass flux density over entire radial direction

(1) mp(z)=∫0∞2πrρp(z,r)wp(z,r)dr=∑j2πrj353TjwjΔrj

where mp(z) is the mass flow rate [kg/s] at measuring height z [m], pp(z,r) is the density of fluid in the plume [kg/m3], wp(z,r) is the vertical downward velocity [m/s] at height z. The subscript j denotes the measuring position in a measuring plane. rj is the radial distance of j-th measuring point [m], Tj is the measured temperature at j-th point [K], wj is the measured vertical downward velocity at j-th point [K], △rj is the interval of measuring point [m]. To estimate the fluid density in the plume, the ideal gas law

(2) ρp=353/Tp

was assumed.

2.2.3 Gas analysis method (GAM)

As shown in Figure 2, CO2 concentrations were measured in supply air, lower layer of fire room, close to gas burner, smoke layer, exhaust smoke and outside. The fuel supply rate to gas burner was measured by a mass flow meter. Air supply and smoke exhaust rates were measured by orifice flow meters. Using these measurements, it is possible to calculate the mass flow rate of downward plume penetrating the smoke layer and entering lower layer.

Considering the conservation of total mass and CO2 mass of the downward plume, fire plume from gas burner, smoke layer, lower air layer and the exhaust gas, simultaneous equations for mass flow rates of downward plume, fire plume, incoming and outgoing vent flows are obtained. By solving for mass flow rates of downward plume entering lower layer, the following equation is derived[10]

(3) mdp=msup+F-Ya,pYs-Ya,pmf-Yex-YaYs-Yamex

where mdp is the mass flow rate of downward plume entering lower layer [kg/s], msup is the rate of air supply from the outlet [kg/s], mf is fuel (natural gas) supply rate to gas burner [kg/s], mex is the rate of exhaust from the upper smoke layer [kg/s], F is the CO2 generation ratio of fuel gas [2.88 kg-CO2/kg-fuel], Ys, Ya, Ya,p, Yex, are the CO2 concentrations in the upper smoke layer, in the lower air layer, in the zone of air entrainment by the gas burner and in the exhaust gas. All the quantities in the right-hand side of Eq. (3) were measured to obtain the mass flow rate of downward plume arriving at lower layer.

2.3 Experimental conditions

The experimental conditions are shown in Table 1. The height of gas burner, depth of smoke curtain and size of outlet were fixed in all the experiments. The heat release rate and smoke exhaust rates were adjusted so that the average temperature of smoke layer would be 20 or 40 K above ambient.

Experimental Conditions

In the experiments 5,6,7 and 11, the temperature difference was set to approximately 20 K. Air supply velocity was adjusted in the range of 1.16 to 2.86 m/s. Heat release rate from gas burner was adjusted in the range of 0.941 to 1.075 kW. Smoke exhaust rate was adjusted in the range of 0.00673 to 0.00866 m3⁄s. As a result, smoke layer thickness was varied in the range of 332 to 536 mm. In the experiment 5, only DMM was applied, while both DMM and GAM were applied in the experiments 6, 7 and 11.

In the experiments 8,9 and 10, the temperature difference was set to approximately 40 K. Air supply velocity was adjusted in the range of 1.56 to 2.78 m/s. By adjusting heat release rate of fire source in the range of 1.748 to 1.882 kW, smoke exhaust rate in the range of 0.00971 to 0.01193 m3⁄s, smoke layer thickness was varied in the range of 416 to 590mm. Both DMM and GAM were applied to these experiments.

In experiment 12, the temperature difference was set to 36.2K. Air supply velocity was varied in the range of 0.44 to 2.6 m/s. No measurements of velocity were made but visual observations were carried out using smoke particle tracer.

3. Experimental Results

3.1 An example - Exp. No.6, temperature difference 22.1 K, air supply velocity 1.65 m/s

As an example, the results of experiment No.6 are demonstrated. Temperature difference between smoke layer and supply air was 22.1 K. Air supply velocity was 1.65 m/s. The results of direct measurement method (DMM) are shown in Figure 5. Downward velocity profile is shown in Figure 5(a). Temperature profile is shown in Figure 5(b). The profiles cover the area of 500 mm × 500 mm where the traverse device could move. Both in Figures 5(a) and 5(b), downward plume can be clearly observed at the center of the diagrams. As the cold air entrains surrounding smoke, the plume velocity is decreased as it goes downward. Temperature is increased as it goes downward and mixed with surrounding smoke layer. The radius of the downward plume is increased as it goes downward.

Figure 5.

Results of direct measurements in Exp. No.6.

As shown in Figure 5(c), the axial velocity was almost constant at 0-100 mm below the supply outlet. After that, axial velocity decreases monotonically according to the distance from the supply outlet. The decrease seemed to be inversely proportional to the distance. The axial temperature was increased gradually. At 300 mm below the outlet, axial temperature was higher than the surrounding temperature measured by the thermocouple tree. It was expected that the axial temperature got close to surrounding air according to distance. However, no asymptotical behavior was found within the measured range.

In Figure 5(d), mass flow rate measured by DMM is plotted against the distance from the outlet. Filled circles denote the value calculated by using dynamic pressures measured by Pitot tube. Open circles denote the measurements by hot wire anemometers. At 200 mm, open and filled circles coincide. In this measurement, Pitot tube was used at the points close to central axis. Hot wire anemometer was used at perimeter where gas temperature was relatively low. As the distance from the outlet increased, vertical velocity profile got flattened and mass flow rates increased considerably due to the increase in plume radius. The mass flow rate increased exponentially with the distance from the outlet. The increase is intense below the smoke layer interface determined by integral ratio method where temperature difference between the downward plume and surrounding air is small.

The results of gas analysis method (GAM) are shown in Figure 6. The values in boxes denotes the measured value. The other values were calculated. As the downward plume went through the smoke layer, the mass flow rate was increased to 19.6 g/s. The mass flow rate of supply air was 3.43 g/s. Thus 16.2 g/s of smoke is entrained into the downward plume and went into lower layer and contaminated the lower layer.

Figure 6.

Results of gas analysis measurements in Exp. No.6.

3.2 Relationship between air supply velocity and mass flow rate

The mass flow rates measured by DMM are summarized in Figure 7. Figure 7(a) shows the results for temperature difference 20 K. In case of air supply velocity 2.8 m/s, increase of mass flow rate is significant in the range of 0-300 mm below the outlet. At more than 300mm below the outlet, the increase was mild. In case of other supply velocities, the mass flow rates increased significantly below 300 mm from the outlet. In case of air supply velocity 1.2 m/s, the increase of mass flow rate was stopped below 400 mm. This is because the plume velocity was decreased according to the distance from the outlet. Because the plume radius was increased, measurement might be inaccurate for this case.

Figure 7.

Mass flow rates at all the experiments.

Figure 7(b) shows the results for temperature difference 40 K. In all the cases, the mass flow rates were significantly increased below 300mm from outlet. As the air supply velocity is increased, increase of mass flow rate was significant. Especially in case of 2.8 m/s air supply velocity, the increase was quite large. Below 500 mm from the outlet, the mass flow rates seem to be scattered. This is because the velocity was too small to make precise measurements.

Comparing Figures 7(a) and 7(b), the effect of temperature difference was slightly observed. Even though the scatter of the data, the mass flow rates are larger in case of 40 K temperature difference.

Using the data in Figure 7, The mass flow rates were compared with existing formulae for forced or thermal plume. The formula in comparison were Morton’s profile method, isothermal forced jet, Zukoski’s upward thermal plume and Hino’s non-isothermal forced plume.

3.2.1 Morton’s profile method

The classical Morton’s profile method for a plume over a point heat source[5] was applied to downward plume. The conservation of mass, momentum and enthalpy are given as follows

(4) ddz[2π∫0∞ρdpwdprdr]=-2πρe(rvp)r→∞
(5) ddz[2π∫0∞ρdpwdp2rdr]=2πg∫0∞(ρdp-ρe)rdr
(6) ddz[2π∫0∞ρdpcp(Tdp-T∞)wdprdr]=-2πρe(rvdp)r→∞cp(Te-T∞)

where z is the vertical distance from outlet [m], r is the radial distance from plume axis [m], pdp(z,r) is the density of fluid [kg/m3], pe(z) is density of ambient fluid [kg/m3], wdp(z,r). is the axial velocity [m/s], vdp(z,r) is the horizontal velocity [m/s], Tdp(z,r) is the temperature in the downward plume [K], Te(z) is the ambient temperature [K], T∞ is the reference temperature [K], cp is the specific heat of fluid [kJ/kg K].

By solving the simultaneous ordinary differential equations numerically, centerline axial velocity, plume radius, centerline temperature and fluid density are obtained. Using the values, the mass flow rate is calculated by

(7) mdp(z)=πB(z)2wdp(z,0)ρp(z,0)

where mdp(z) is the mass flow rate of plume [kg/s], B(z) is the characteristic radius of plume [m].

3.2.2 Isothermal forced jet

The isothermal forced jet equations[13] are commonly used in the design of air supply to large spaces. In the far field from an outlet, the axial velocity of plume is given by

(8) wdp(z,0)=K′Azwdp(0,0)

where K' is the outlet coefficient (= 5.0 for squared outlet), is the opening area of outlet [m2]. The radial distribution of velocity is approximated by the following Gaussian profile as

(9) wdp(z,r)=e-π2K′2(rz)2wdp(z,0).

Then, the mass flow rate is given by

(10) mdp(z)=∫0∞2πρdpwdprdr=2ρdp(z)AK′wp(z,0)   z

where pp0(z) is the density of fluid at central axis [kg/m3],

3.2.3 Zukoski’s thermal plume

The original Zukoski’s formula was developed to express the mass flow rate of upward buoyant thermal plume [14].

(11) mdp=0.076Q13(z+z0)53

where mp(z) is the mass flow rate [kg/s], Q is the heat release rate of fire source [kW], z0 is the position of virtual origin [m]. To apply to downward plume, the heat release rate was replaced by the deficiency of enthalpy as defined in Eq. (12). The virtual origin was located so that the mass flow rate at the outlet equals the flow rate calculated by Eq. (11) at z=0 as defined by Eq. (13).

(12) Q=cp(Ts-Tsup)msup,
(13) z0={msup20.0763cp(Ts-Tsup)}15,

where msup is the air supply rate [kg/s], Ts is the smoke layer temperature [K], Tsup is the supply air temperature [K].

3.2.4 Hino’s forced plume

Hino developed a set of formulae for a forced plume[6] in an environment with constant vertical density gradient. The conservation equations of mass, momentum and fluid density are

(14) ∂wp∂z+∂vp∂r+vpr=0
(15) ∂ρpwp2∂z+1r∂(rρwpvp)∂r=1r∂(rτ)∂r-g(ρp-ρe)
(16) wp∂ρp∂z+vp∂ρp∂r=-1r∂r(vpρp¯)∂r

where wp is the axial velocity [m/s], vp is the radial velocity [m/s], pp and pe are the densities of fluid in the plume and in the ambient air, respectively, τ is the shear stress [Pa/m2], and are the axial and radial coordinates [m]. The equations were solved analytically and resulted in a set of formula for volume flow rate. Skipping the details, the final result is

(17) mdp=πB2wp(z,0)ρp(z,0)

where B(z) is the characteristic radius of plume [m].

Figure 8 shows the comparison results. Isothermal jet formula and Hino’s forced plume formula result in much larger values than the experiments. Morton’s profile method and Zukoski’s formula result in good agreements. Especially the slope of regression is close to 1 in case of Zukoski’s formula. Judging from the result, Zukoski’s formula is the best to correlate the results, and that Morton’s profile method is usable as well.

Figure 8.

Comparison of calculated and measured mass flow rates for all the experimental data.

The Zukosky’s formula is compared in detail in Figure 9. Dividing Eq. (11) by Q1/3, the data were plotted by mdp/Q1/3 versus z. Regardless of the air supply velocity and supply temperature, the results seem to agree with the formula.

Figure 9.

Comparison of mass flow rates with Zukoski’s formula.

3.3 Yield to lower layer

3.3.1 Definition

After penetrating through the smoke layer, most of the plume mass enters the lower air layer, but part of the mass goes back to smoke layer due to buoyancy. To consider the degree of contamination of lower layer, yield ratio should be discussed. The yield ratio is defined by the ratio of mass entering the lower layer to the mass penetrated the smoke layer as shown in Figure 10.

Figure 10.

Flow pattern at the bottom of smoke layer.

3.3.2 Measured results

The mass flow rate of smoke entrained by the downward plume and yielded to lower layer was measured by GAM. Mass flow that went back to upper layer due to buoyancy is not included in the measured value. The results for temperature difference 20 K (experiments No. 6,7 and 11) are shown in Figure 11(a) as functions of supply air velocity. As the supply velocity increased, the mass flow rates yielded to lower layer was increased linearly. On the other hands, the entrained smoke mass flow rate was decreased. This is because the smoke layer thickness was 437 mm in case of 2.2 m/s of supply velocity, which was thinner than the other two experiments.

Figure 11.

Flow rate yielded to lower layer measured by GAM.

In case of temperature difference 40 K, the results for experiments 8, 9 and 10 are shown in Figure 11(b). Similar to the case of temperature difference 20 K, mass flow rates yielded to lower layer had increased according to air supply velocity. In case of 2.8 m/s of supply velocity, the mass flow rate was decreased. This is also because the smoke layer was thinner than the other two experiments.

To investigate the yield ratio to lower layer, results of DMM and GAM were used to calculate the yield ratio. By GAM, mass flow rate yielded to lower layer is obtained as in Figure 11. On the other hand, DMM gives total mass flow rate at the bottom of smoke layer as was shown in Figure 7. By taking the fraction, the yield ratio was calculated by

(18) R=mass flow rate yielded to lower layer by GAMmass flow rate by DMM at the bottom of smoke layer

The results are shown in Figure 12. The ratio is around 0.7 to 1. The ratio tends to decrease as the air supply velocity is increased. In case of 1.2 m of air supply velocity, the ratio exceeded 1 because of measurement error. This is because the smoke layer was thick, and the plume velocity was small when the plume arrived at the bottom of smoke layer. In case of temperature difference 40 K, the tendency is smooth and decreased as the air supply velocity is increased.

Figure 12.

Yield ratio to lower layer.

3.3.3 Relationship with the velocity at the bottom of smoke layer

The relationship between the plume velocity at the bottom of smoke layer and the yield ratio to the lower layer is shown in Figure 13. The velocity at the bottom of smoke layer was not explicitly measured but calculated by the isothermal jet flow equation[13] because the better correlation is obtained with experimental measurements for axial velocity. Yield ratio was calculated by Eq. (18), but Zukoski’s formula was used instead of the mass flow rate by DMM at the bottom of smoke layer to reduce the effect of experimental scatter.

Figure 13.

Relationship between the plume velocity at the bottom of smoke layer and the yield ratio to lower layer.

It was expected that the yield ratio is increased as the velocity at the bottom of smoke layer is increased. However, as seen in Figure 13, yield ratio was maximum when the velocity at the bottom of smoke layer was minimum (0.12 m/s) in case of temperature difference 20K. In case of temperature difference 40 K, the yield ratio was increased monotonically as the velocity at the bottom of smoke layer was increased. In comparison between temperature difference 20 K and 40 K, yield ratio was smaller in case of temperature difference 40 K. This is because of the difference in buoyancy. In case of large temperature difference, downward plume entrains high temperature smoke, and plume temperature got higher. After penetration to lower layer, the plume gas was easy to go back to smoke layer due to buoyancy.

3.3.4 Relationship with the temperature at the bottom of smoke layer

The relationship between the plume axial temperature at the bottom of smoke layer and the yield ratio is shown in Figure 14. The plume axial temperature was calculated by the enthalpy conservation of the downward plume.

Figure 14.

Relationship between the plume temperature at the bottom of smoke layer and the yield ratio to lower layer.

(19) Tdp(zs)=Ts-msupmdp(zs)(Ts-Tsup)

where mdp(zs) is the mass flow rate of downward plume at the bottom of smoke layer [kg/s]. Eq. (11) is used for mdp(zs. As seen in Figure 14, yield ratio decreases as the plume temperature at the bottom of smoke layer is increased. The yield ratio at 15K temperature difference is maximum but it seems to decrease with the temperature difference as a general tendency.

3.3.5 General relationship by Froude number

To derive general relationships among temperature, velocity at the bottom of smoke layer and yield ratio, Froude modelling is discussed. At the bottom of the smoke layer, downward plume penetrated out of the smoke layer. Using white dust particles, the flow was visualized in the experiment 12 as shown in Figure 15. Head of downward plume penetrates. The head is mixed with lower layer air and contaminates the lower layer air. The rest of the mass goes back to smoke layer.

Figure 15.

Visualized image of flow at the bottom of smoke layer (experiment 12, air supply velocity 1.4 m/s).

The degree of mixing could be modelled by Froude number determined by

(20) Fr=wdp(zs)β(Tdp(zs)-Ta)ght

where Tdp(zs) is the axial centerline temperature of downward plume at the bottom of smoke layer [K], Ta is the lower layer temperature [K], g is the gravitational acceleration [m2/s], b is the volume expansion ratio (=1/Ta) [K-1]. The maximum arrival distance below smoke layer [m] was calculated assuming that the kinetic energy at the bottom of smoke layer is converted to negative buoyancy head as,

(21) hl=12ρwp02/{β(Tdp(zs)-Ta)g}

where wp0 is the axial velocity of downward plume at the bottom of smoke layer [m/s]. The velocity was calculated by the isothermal jet flow equation[13] same with the analysis for Figure 13.

Using the data in Figure 14, correlation between yield ratio and Froude number was derived for DT = 20 K (experiments 6,7 and 11) and DT = 40 K (experiments 8-10). The results are shown in Figure 16. In case of DT = 20 K, the yield ratio tends to increase with the Froude number. ratio of However in case of DT = 40 K, yield ratio is generally smaller than the case of DT = 20 K. Converse with the case of DT = 20 K, the ratio tends to decrease with the Froude number. If the degree of mixing at the penetrated core of downward plume is considered, the yield ratio should increase with the Froude number. However, experimental results did not show clear relationships. Tentatively, it is hard to derive a quantitative relationship between Froude number and yield ratio, it can be said that the yield ratio is around 0.8 to 1.0.

Figure 16.

Relationship between the Froude number and the yield ratio to lower layer.

4. Conclusions

The characteristics of downward plume was examined by model scale experiments and comparison with plume formulae. The main findings are as follows.

(1) The mass flow rate of downward plume was measured by direct measurement method of velocity and temperature profile across the plume section. The mass flow entering the lower layer was measured by gas analysis method derived from conservation of total mass and CO2 mass.

(2) The entrainment rate of downward plume can be expressed by Zukoski’s formula with replacement of the heat release rate by deficiency of enthalpy of supplied air relative to smoke layer temperature.

(3) After the downward plume penetrated the smoke layer, part of the plume goes back to smoke layer. The rest is yielded to lower air layer. The ratio of yield to lower layer was measured and correlated with the Froude number at the bottom of smoke layer. The ratio is fairly constant over Froude number and the average value is around 0.8.

Notes

Author Contributions

Conceptualization, K. Harada. and D. Nii; methodology, K. Harada.; software, H. Tsuji.; data curation, H. Tsuji; writing-original draft preparation, H.Tsuji.; writing-review and editing, K. Harada.; visualization, H. Tsuji and D. Nii.; supervision, K. Harada.; project administration, K. Harada.; funding acquisition, K. Harada. All authors have read and agreed to the published version of the manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

References

1. Seeburger D., Nute K., Emberley R., Torero J. L.. Impact of Air Handling Velocities on Smoke Behavior and Management. In : Proceedings of the 3rd International Fire Safety Symposium. IFireSS 2019, Ottawa, Ontario, June 5-7. 550–567. 2019.
2. Audouin L., Rigollet L., Prétrel H., Saux W. Le, Röwekamp M.. OECD PRISME Project: Fires in Confined and Ventilated Nuclear-Type Multi-Compartments-Overview and Main Experimental Results. Fire Safety Journal 62:80–101. 2013;https://doi.org/10.1016/j.firesaf.2013.07.008.
3. Hitachi-GE Nuclear Energy, Ltd.. Hokiaburakasaiwo moshita jitsukibo nenshojikken (Full scale experiments simulating an oil spill fire from an auxiliary machines). HLR-115rev1 2014;
4. Prétrel H., Saux W. Le, Audoui L.. Pressure Variations Induced by a Pool Fire in a Well-Confined and Force-Ventilated Compartment. Fire Safety Journal 52:11–24. 2012;https://doi.org/10.1016/j.firesaf.2012.04.005.
5. Morton B. R.. Forced Plume. Journal of Fluid Mechanics 5(1):151–163. 1959;https://doi.org/10.1017/S002211205900012X.
6. Hino M.. Forced Plumes in a Stably Stratified Fluid. Proceedings of JSCE 86(10):29–37. 1962;
7. Kubota H.. Daikuukanhe Suityokuni Fukidasu Hitouonkiryuuno Kaiseki (An Analysis of Non-Isothermal Plume Vertically Ejected to a Large Space). Journal of the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan 47(9):35–41. 1973;
8. Koestel A.. Computing Temperatures and Velocities in Vertical Jets of Hot or Cold Air. ASHRAE Transactions 60:385–410. 1954;
9. P. Kofoed and P. V. Nielsen, "Thermal Plumes in Ventilated Rooms: Measurements in Stratified Surroundings and Analysis by Use of an Extrapolation Method", Indoor Environmental Technology, Vol. R9043, No. 14, Dept. of Building Technology and Structural Engineering, Aalborg University (1990).
10. H. Ichikawa, H. Tsuji, K. Harada and D. Nii, "Measurement of Smoke Entrainment Rate by a Downward Plume", Presented at AOSFST 2021 - 12th Asia-Oceania Symposium on Fire Science and Technology, The University of Queensland, Brisbane, Australia (2021).
11. Cooper L. Y., Harkleroad M., Quintiere J. G., Rinkinen W.. An Experimental Study of Upper Hot Layer Stratification in Full-Scall Multiroom Fire Scenarios. Journal of Heat and Mass Transfer 104(4):741–749. 1982;https://doi.org/10.1115/1.3245194.
12. He Y., Fernando A., Luo M.. Determination of Interface Height from Measured Parameter Profile in Enclosure fire Experiment. Fire Safety Journal 31:19–38. 1998;https://doi.org/10.1016/S0379-7112(97)00064-7.
13. American Society of Heating, Refrigerating and Air-Conditioning Engineers, "ASHRAE Handbook, Fundamentals" (1985).
14. Zukoski E. E., Kubota T., Cetegen B.. Entrainment in Fire Plume. Fire Safety Journal 3:107–121. 1981;https://doi.org/10.1016/0379-7112(81)90037-0.

Article information Continued

Figure 1.

Schematics of downward plume.

Figure 2.

Schematics of the experimental setup (unit: mm).

Figure 3.

Inner view of the fire room.

Figure 4.

measuring planes of direct measuring method (DMM).

Figure 5.

Results of direct measurements in Exp. No.6.

Figure 6.

Results of gas analysis measurements in Exp. No.6.

Figure 7.

Mass flow rates at all the experiments.

Figure 8.

Comparison of calculated and measured mass flow rates for all the experimental data.

Figure 9.

Comparison of mass flow rates with Zukoski’s formula.

Figure 10.

Flow pattern at the bottom of smoke layer.

Figure 11.

Flow rate yielded to lower layer measured by GAM.

Figure 12.

Yield ratio to lower layer.

Figure 13.

Relationship between the plume velocity at the bottom of smoke layer and the yield ratio to lower layer.

Figure 14.

Relationship between the plume temperature at the bottom of smoke layer and the yield ratio to lower layer.

Figure 15.

Visualized image of flow at the bottom of smoke layer (experiment 12, air supply velocity 1.4 m/s).

Figure 16.

Relationship between the Froude number and the yield ratio to lower layer.

Table 1

Experimental Conditions

Exp. No *1. Smoke Layer Thickness *2 Temp. Difference *3 Outside Temp. HRR Air Supply Rate Air Supply Velocity Smoke Exhaust Rate DMM *4 GAM *5
mm °C °C kW m3/s m/s m3/s - -
No. 5 332 21.0 21.2 1.075 0.00525 2.86 0.00673 Yes No
No. 6 528 22.1 17.0 0.941 0.00282 1.65 0.00801 Yes Yes
No. 7 437 24.3 18.1 1.075 0.00394 2.20 0.00866 Yes Yes
No. 8 439 38.9 18.0 1.882 0.00526 2.76 0.00971 Yes Yes
No. 9 541 38.3 16.1 1.815 0.00282 1.56 0.01122 Yes Yes
No.10 590 36.0 17.2 1.815 0.00398 2.09 0.00979 Yes Yes
No. 11 536 22.5 14.1 0.941 0.00199 1.16 0.00808 Yes Yes
No. 12 416 36.2 13.7 1.748 0.00077 to 0.00477 0.44 to 2.60 0.01056 to 0.01193 No No
*

1: Exp. 1 to 4 are provisional. *2: by N%-method (N = 0.23) *3: temperature difference between smoke layer and supply air. *4: Direct measurement method. *5: Gas analysis method