Lee: A Study on the Operational Status and Improvement Measures of Fire Doors in High-Rise and Super High-Rise Buildings

Abstract

Recently, the importance of evacuation safety and smoke control in high-rise and super high-rise buildings has been increasingly emphasized due to the growth of mixed-use commercial buildings and large underground parking structures. However, previous studies have mainly focused on the fire resistance performance and structural characteristics of fire doors, whereas field investigations of their actual operational and maintenance conditions remain limited. Therefore, this study investigated the operational and maintenance status of fire doors in 33 high-rise and super high-rise buildings 30 stories or more. The investigation focused on fire doors located in stairwells, evacuation elevator lobbies, basement parking connections, common corridors, and refuge floors through on-site inspections, operational testing, and photographic documentation. The investigation identified various problems, including permanently open fire doors, removal of automatic closing devices, fire door deformation and failure to close properly, obstruction of evacuation routes by stored items, and damage to fire compartmentation. In particular, maintenance problems were repeatedly identified in evacuation elevator lobbies and ancillary rooms of special evacuation stairwells. Older buildings exhibited more frequent problems of deformation, sagging, and sealing failures, whereas residential complexes and officetels frequently exhibited storage-related problems in common areas and evacuation routes. Based on these findings, this study proposed improvement measures, including expanding detector-linked automatic closing systems, strengthening fire door maintenance and inspection requirements, reinforcing evacuation route management, considering occupant behavior and actual building usage characteristics, and improving practical evacuation information and awareness regarding fire compartmentation and fire door management.

1. Introduction

Recently, urban environments in the Republic of Korea have become increasingly dense and complex, leading to a rapid increase in the construction of high-rise and super high-rise buildings. In particular, super high-rise mixed-use buildings centered on commercial occupancies, such as office facilities, accommodation facilities, and officetels (mixed-use residential and office buildings), have become more common, along with building designs integrating large-scale underground parking areas and vertical evacuation routes. Although these high-rise buildings offer advantages in terms of land-use efficiency and space utilization, they also present challenges, including an increased potential for vertical smoke and heat spread and prolonged evacuation times during fire incidents. In particular, in buildings where underground parking lots, stairwells, and evacuation elevator lobbies are interconnected, smoke control and the protection of evacuation routes become critical safety considerations. In recent fire incidents involving apartment buildings and commercial facilities, evacuation difficulties caused by smoke spread have repeatedly emerged as more significant concerns than the fire itself. Representative domestic underground parking lot fire incidents have raised major concerns regarding large-scale smoke spread and occupant evacuation, whereas overseas incidents, such as the Tai Po Wang Fuk Court fire in Hong Kong, have highlighted concerns regarding the risk of fire spread associated with inadequate fire compartmentation and fire door management [1,2].
In high-rise building fires, fire doors are not merely access doors but essential fire safety and evacuation facilities that maintain fire compartmentation and prevent smoke spread. In particular, fire doors installed in ancillary rooms of special evacuation stairwells and evacuation elevator lobbies play an important role in preventing smoke infiltration into stairwells and protecting evacuation routes. However, during routine building operation, fire doors are often permanently left open, and door closers are frequently removed for user convenience, resulting in the loss of fire compartmentation performance. Current building regulations and fire safety codes specify standards for fire door construction, self-closing performance, and opening direction for evacuation; however, studies investigating their actual operational and maintenance status remain relatively limited. Previous studies have mainly focused on fire performance testing and regulatory analyses, whereas field investigations analyzing the operational conditions and maintenance problems of fire doors in high-rise buildings remain scarce [3-8].
Therefore, this study aims to investigate the operational status of fire doors in high-rise and super high-rise buildings, analyze maintenance problems and cases of fire compartmentation damage, and propose improvement measures to enhance evacuation safety. In addition, this study examines discrepancies between the current evacuation and fire protection systems and actual operational conditions.

2. Literature Review

2.1. Importance of fire doors

Fire doors are essential fire protection and evacuation facilities designed to maintain the integrity of fire compartmentation by preventing the spread of flames and smoke during fire incidents and securing evacuation time for occupants. In particular, in high-rise and super high-rise buildings, fire doors installed in ancillary rooms of special evacuation stairwells, evacuation elevator lobbies, and basement parking connections play important roles in preventing smoke spread and ensuring evacuation safety. To fulfill these functions, fire doors are required to provide adequate fire resistance and smoke leakage performance, which are verified through standardized testing methods and performance criteria [9-15]. In high-rise building fires, stairwells serve as the final evacuation route and become the primary spaces for the vertical evacuation of occupants during fire emergencies. Therefore, preventing smoke infiltration into stairwells and maintaining tenable evacuation conditions are critical. In particular, fire doors installed in ancillary rooms of special evacuation stairwells and evacuation elevator lobbies serve as key facilities for preventing smoke infiltration from fire compartments into stairwells. However, when fire doors are permanently left open or their self-closing functions are not properly maintained, the risk of smoke infiltration into stairwells increases significantly. In addition, open fire doors can adversely affect smoke control systems and differential pressure maintenance, potentially reducing the overall evacuation safety performance of high-rise buildings. Therefore, stairwell fire doors should not be regarded merely as access doors but as essential fire safety facilities for protecting evacuation routes, requiring continuous maintenance and proper closure at all times [16-19].

2.2. Legal framework for evacuation and fire protection in high-rise buildings

The legal framework governing evacuation and fire protection in high-rise buildings in the Republic of Korea is primarily composed of the Building Act, the Act on the Installation and Management of Firefighting Systems, and the Rule on the Standards for Egress and Fire-Proof Structures of Buildings. In particular, the Building Act stipulates architectural fire protection requirements for special evacuation staircases, evacuation elevators, fire compartmentation, and fire doors, whereas the Act on the Installation and Management of Firefighting Systems provides requirements for securing evacuation safety through smoke control systems, alarm systems, and fire extinguishing systems [11-15]. In high-rise and super high-rise buildings, the installation of special evacuation staircases and evacuation elevators is mandatory, and fire doors installed in stairwells and ancillary rooms are designated as essential facilities for preventing smoke spread during fire incidents. Major regulations related to fire doors include Article 49 of the Building Act concerning evacuation facilities and occupancy restrictions; Article 48 of the Enforcement Decree of the Building Act concerning installation standards for stairways, corridors, and exits; Article 64 of the Enforcement Decree of the Building Act concerning the classification of fire doors; Article 9 of the Rule on the Standards for Egress and Fire-Proof Structures of Buildings concerning the structure of evacuation staircases and special evacuation staircases; and Article 26 of the same Rule concerning fire door construction [11-13]. In addition, fire doors are required to maintain self-closing performance, the appropriate opening direction for evacuation, and smoke control performance while preserving fire compartmentation during fire incidents [14-18].

2.3. Review of previous studies

As shown in Table 1, studies on the performance maintenance and management of fire doors have been conducted continuously in the Republic of Korea in recent years. Early studies mainly focused on the construction quality and fire performance of fire doors. Seo et al. [3] analyzed pre-completion safety inspection records and fire performance test data and identified field quality control problems, such as missing door closers, excessive fire door gaps, and missing hardware components. In addition, Shim and Park [5] conducted a statistical analysis of fire resistance test data for fire doors installed in evacuation spaces and common areas of apartment buildings and analyzed their structural characteristics and the major factors influencing fire door performance. Subsequent studies expanded their focus to the maintenance, durability, and management of fire doors. Yoon [4] analyzed major litigation cases related to fire door performance and identified key issues concerning durability, maintenance responsibility, performance verification procedures, and the scope of defect repairs. The study emphasized the importance of periodic inspection and maintenance systems for ensuring long-term fire door performance. Kim et al. [6] analyzed fire door operation probabilities and expert survey results and reported that fire doors older than 15 years exhibited increasing failure rates. The major deterioration factors included twisting, corrosion, dents, and physical damage. Recently, field investigations of actual operational conditions and occupant behavior have also increased. Kim and Lee [7] conducted a checklist-based field investigation of stairwell fire doors in apartment buildings and reported that a significant proportion of abnormal fire door opening conditions resulted from intentional fixing. The study also indicated that the frequency of fire door opening and abnormal conditions increased with building age. In addition, the authors suggested that increased storage of items in surrounding areas could be associated with permanently open fire doors. In addition to field investigations of operational conditions, studies investigating the deterioration of actual fire resistance performance have also been conducted. Kim [8] analyzed fire resistance test results for apartment fire doors and found that fire door performance failure rates tended to increase with building age.
However, most previous studies have been conducted on apartment buildings and have focused on residential entrance doors, common-area fire doors, and stairwell fire doors. In addition, previous studies have primarily addressed the fire resistance performance, structural characteristics, and aging-related problems of fire doors, whereas studies investigating the actual operational conditions and field maintenance status of fire doors in high-rise and super high-rise buildings remain relatively limited. In particular, studies investigating fire compartmentation maintenance problems in evacuation elevator lobbies, refuge floors, common corridors, and mixed-use buildings have been limited, and field investigations targeting high-rise and super high-rise buildings with mixed occupancies, such as commercial facilities, accommodation facilities, and office facilities, remain scarce.

3. Research Methodology and Surveyed Buildings

3.1. Scope of the study and investigation method

This study was conducted to investigate the operational status of fire doors and analyze related problems in high-rise and super high-rise buildings 30 stories or more. Rather than focusing on the structural fire performance of fire doors, this study primarily examined their actual operational conditions and maintenance status. The investigation focused primarily on the condition of fire doors in ancillary rooms of special evacuation stairwells, evacuation elevator lobbies, basement parking connections, and corridors. During the investigation, architectural drawings were first reviewed to identify the fire compartmentation layout and the installation locations of fire doors. Subsequently, on-site inspections were conducted to examine the maintenance status of the fire doors. In addition, operational testing was performed on selected fire doors to verify their self-closing performance and normal operation, and major deficiencies were documented through photographic records. As shown in Table 2, the main investigation items included fire door closing conditions, maintenance of self-closing functions, maintenance of fire compartmentation, and management of evacuation routes. The investigation was not conducted as a comprehensive inspection of all floors in the surveyed buildings. Instead, a sampling-based investigation method was applied by dividing each building into lower, middle, and upper sections according to its height. However, when recurring problems, such as malfunctioning self-closing functions, permanently open fire doors, and damage to fire compartmentation, were identified during the investigation, the scope of the investigation was expanded to include multiple floors or nearly the entire building.

3.2. Overview of the investigated buildings

Table 3 presents an overview of the buildings investigated in this study. The survey targeted all high-rise and super high-rise buildings with 30 stories or more located in Haeundae-gu, Busan, Republic of Korea, and a full census survey was conducted for all buildings that met the selection criteria at the time of the investigation. The investigated buildings included office facilities, officetels, accommodation facilities, and a factory facility, and field investigations were conducted for a total of 33 buildings. In terms of occupancy type, the investigated buildings comprised 15 office facilities, 9 accommodation facilities, 8 officetels, and 1 factory facility. The approval years of the investigated buildings ranged from 2003 to 2024, and the building heights ranged from 30 to 94 stories. In addition, the floor area ratio ranged from approximately 457% to 1,321%, whereas the building coverage ratio ranged from approximately 13% to 80%. Figure 1 illustrates the distribution of the investigated buildings according to elapsed years, number of stories, floor area ratio, and building coverage ratio. The investigation results showed that buildings with 30-39 stories accounted for the largest proportion of the surveyed buildings, whereas floor area ratios were most frequently distributed within the range of 800%-999%.

4. Results of Field Investigation

The field investigation results indicated that fire door maintenance problems in high-rise and super high-rise buildings could generally be classified into several categories, including permanently open fire doors, maintenance problems involving fire doors in evacuation elevator lobbies, storage-related misuse of common spaces, fire door deformation and failure to close properly, and limitations in maintenance and inspection systems.
Figure 2 presents representative examples of permanently open and intentionally fixed-open fire doors. The investigation repeatedly identified permanently open fire doors at first-floor entrances, basement parking connections, and evacuation elevator lobbies. In many cases, fire doors were intentionally fixed open using fire extinguishers, wedges, or door stoppers. In some buildings, fire doors were routinely kept in a permanently open condition, and these problems were associated with user convenience and freight movement activities, such as moving and delivery operations.
Figure 3 presents examples of fire door deformation and maintenance problems. Cases involving the removal of fire doors, fire door deformation, defective door handles, and malfunctioning door closers were identified in several buildings. In particular, older buildings exhibited relatively frequent problems, such as sagging fire doors, excessive gaps, and sealing failures. In addition, some fire doors failed to open or close properly because of wind pressure effects.
Figure 4 presents examples of storage-related obstructions in evacuation routes and common spaces. In residential complex buildings and officetels, bicycles, household goods, and parcel deliveries were frequently found in evacuation routes and common areas. In some buildings, portions of common corridors and evacuation spaces were effectively used as private storage areas. In addition, stored items in ancillary rooms of special evacuation stairwells and evacuation elevator lobbies reduced the effective width of evacuation routes and obstructed evacuation paths.
Table 4 summarizes representative cases that were repeatedly identified or considered relatively severe during the field investigation, whereas Table 5 provides a comprehensive classification of the major problem types and their underlying causes based on the investigation findings. The investigation indicated that fire door maintenance problems were associated not only with occupant behavior but also with maintenance management systems and inspection practices. In particular, inspections frequently focused on the operational status of detector-linked automatic closing devices, whereas inspections of fire door deformation, permanently open conditions, and the maintenance of fire compartmentation were relatively insufficient.

5. Improvement Directions for Major Problems

Based on the major problems and underlying causes identified in Tables 4 and 5, the following improvement measures are proposed to maintain fire compartmentation and enhance evacuation safety.
First, to address the problem of permanently open and fixed-open fire doors, the application of detector-linked automatic closing devices should be considered for fire doors installed in frequently used locations, such as basement parking connections, first-floor entrances, and evacuation elevator lobbies. In addition, because repeated instances were identified in which fire extinguishers installed in corridors and evacuation routes were used to hold fire doors open, the fixed installation methods for fire extinguishers should be reviewed, and management standards for the areas surrounding fire doors should be strengthened. Furthermore, the installation of information stickers and guidance notices on stairwell and evacuation elevator lobby fire doors should be reinforced to emphasize the prohibition of permanently open fire doors, the importance of maintaining fire doors, and restrictions on non-emergency use. Fire safety planning and fire door operation strategies should also take actual occupant behavior and building usage characteristics during normal operation into account.
Second, regarding maintenance problems involving fire doors in evacuation elevator lobbies, the investigation confirmed that these problems repeatedly occurred during the use of evacuation elevators for freight transport, moving activities, and parcel delivery. In particular, cases involving the removal of automatic closing devices and the intentional fixing of fire doors were identified, indicating the need for further review of maintenance standards and operational management measures for fire doors in evacuation elevator lobbies. In addition, further discussion is required regarding restrictions on the non-emergency use of evacuation elevators and the reinforcement of evacuation elevator lobby management.
Third, regarding storage-related obstructions identified in residential officetels and apartment buildings, enforcement against stored items in evacuation routes and stairwells should be strengthened, while management standards for common spaces should be improved. In particular, repeated cases involving bicycles, household goods, and parcel deliveries were identified, indicating the need to strengthen control over the use of common corridors and evacuation spaces as private storage areas. In addition, enhanced management and inspection of common spaces surrounding lower-floor commercial facilities are also necessary. In particular, management measures should also address stored items that contain combustible materials and potential ignition sources, such as electric mobility devices and lithium-ion battery-powered equipment.
Fourth, regarding fire door deformation and failure to close properly, future maintenance procedures should include inspections not only of the operation of automatic closing devices but also of fire door sagging, excessive gaps, sealing failures, and opening and closing failures caused by wind pressure. In particular, regular maintenance and performance inspections should be strengthened for older buildings and for fire doors installed on the first and top floors, which are directly exposed to outdoor conditions. For lower- and upper-floor areas that are significantly affected by wind pressure, both design considerations and maintenance management should be strengthened to prevent fire door deformation.
Fifth, regarding limitations in fire door maintenance systems and inspection practices, the investigation indicated that current maintenance and fire safety inspection procedures tend to focus primarily on the interlocking operation of automatic closing devices. Therefore, future maintenance procedures should expand inspection items to include fire door structural deformation, permanently open conditions, the maintenance of fire compartmentation, and the management of evacuation routes. In addition, fire door management education for fire safety managers and maintenance personnel should be strengthened, while occupant awareness of the importance of fire doors should also be improved. Furthermore, practical evacuation guidance on refuge floors, evacuation safety zones, and evacuation procedures should be provided continuously to occupants.

6. Conclusion

This study investigated the operational status and maintenance conditions of fire doors in 33 high-rise and super high-rise buildings exceeding 30 stories through field inspections, operational testing, and photographic documentation.
The investigation identified recurring problems, including permanently open fire doors, removal of automatic closing devices, fire door deformation, obstruction of evacuation routes by stored items, and inadequate maintenance practices. In particular, maintenance problems were repeatedly identified in evacuation elevator lobbies and ancillary rooms of special evacuation stairwells, whereas older buildings exhibited relatively frequent problems related to sagging, excessive gaps, and wind pressure effects.
The results also indicated that current maintenance and inspection systems tend to focus primarily on detector-linked automatic closing devices, whereas inspections of structural deformation, permanently open conditions, and the maintenance of fire compartmentation remain insufficient. Accordingly, this study proposed improvement measures, including expanding detector-linked automatic closing systems, strengthening evacuation route management, reinforcing fire door inspection requirements, and improving occupant awareness of fire compartmentation maintenance.
This study provides valuable field investigation findings and practical insights into maintenance problems related to fire door operation in actual high-rise and super high-rise buildings. However, quantitative performance evaluation and validation of the proposed improvement measures were not conducted. Therefore, further studies investigating smoke control performance, differential pressure maintenance, wind pressure effects, and improvements to maintenance systems are needed.

Notes

Author Contributions

Conceptualization, J. Lee; methodology, J. Lee; investigation, J. Lee; formal analysis, J. Lee; data curation, J. Lee; writing—original draft preparation, J. Lee; writing—review and editing, J. Lee. The author has read and agreed to the published version of the manuscript.

Conflicts of Interest

The author declares no conflict of interest.

Figure 1.
Distribution characteristics of the investigated buildings.
KIFSE-6feaf600f1.jpg
Figure 2.
Representative fixed-open conditions of fire doors.
KIFSE-6feaf600f2.jpg
Figure 3.
Examples of fire door deformation and maintenance problems.
KIFSE-6feaf600f3.jpg
Figure 4.
Examples of evacuation route obstruction and improper use of common spaces.
KIFSE-6feaf600f4.jpg
Table 1.
Summary of Previous Studies on Fire Door Maintenance and Field Investigations [3-8]
Year Authors Target building or system Research method Major findings
2016 Seo et al. [3] Fire doors and fire shutters Analysis of pre-completion inspection reports and fire performance test data Identified construction quality problems, such as missing door closers, excessive fire door gaps, improper installation orientation, and missing hardware components.
2021 Yoon [4] Fire door performance litigation cases Analysis of litigation cases and fire door performance disputes Identified major issues related to fire door durability, performance verification procedures, maintenance responsibility, and the scope of defect repairs. Emphasized the need for periodic maintenance and inspection systems.
2022 Shim and park [5] Fire doors in evacuation spaces and common areas of apartment buildings Statistical analysis of a fire resistance test database Identified major factors affecting fire performance, including filler density, adhesive materials, gaskets, and fire fins. The major causes of failure were flame occurrence and gap penetration.
2024 Kim et al. [6] Public fire doors in apartment buildings Fire door operation probabilities analysis and expert survey Fire doors older than 15 years exhibited operation failure rates exceeding 20%. The recommended replacement period was 10-15 years, and the major deterioration factors included twisting, corrosion, dents, and physical damage.
2025 Kim and lee [7] Stairwell fire doors in apartment buildings Checklist-based field investigation and correlation analysis 54.9% of abnormal fire door conditions were caused by intentional fixing. Fire door opening rates and malfunction rates increased with building age and surrounding obstructions.
2026 Kim [8] Fire doors in apartment buildings Analysis of fire resistance test data from defect litigation cases Fire door failure rates increased after 10 years. Problems related to honeycomb core structures and pivot hinges were identified, and life-cycle-based maintenance was recommended.
Table 2.
Main Investigation Items
Category Investigation items
Fire door condition Door deformation, damage, and removal status
Self-closing function Door closer operation and automatic closing performance
Fire compartmentation Maintenance of fire compartment boundaries
Open fixing condition Fixed-open condition and obstruction status
Evacuation route management Storage-related obstructions and evacuation interference
Field verification On-site inspections, operational testing, and photographic documentation
Table 3.
Overview of Surveyed Buildings
Category Description
Number of buildings surveyed 33 buildings
Super high-rise buildings 3 buildings
High-rise buildings 30 buildings
Occupancy type 15 office buildings, 9 accommodation facilities, 8 officetels, and 1 factory facility
Floor range 30-94 stories
Approval year range 2003-2024
Floor area ratio range Approximately 457%-1,321%
Building coverage ratio range Approximately 13%-80%
Main survey areas Special evacuation staircases, evacuation elevator lobbies, refuge areas, basement parking connections, and corridors
Survey period December 2025-march 2026
Table 4.
Summary of Representative Fire Door Problems Identified During the Field Investigation
Occupancy type Approval year Self-closing failure Door closer defect Fire door failure Fixed-open condition Fire compartmentation damage Evacuation route obstruction Other problems
Of 2003 - - - - - - -
Of 2005 O O - - O O Fire door removed
Af 2005 - - - - - - -
Of 2006 - - - O - - -
Of 2006 - - O - - O Full-floor inspection of the evacuation elevator lobby entrances
Of 2007 - O O - - - Defects in evacuation elevator lobby fire doors
Af 2008 O O - - - - -
Of 2009 O O O - O O Removal of emergency evacuation elevator lobby fire doors
Af 2013 - O - - - - Use of composite panel exterior cladding
Af 2015 - O O - - O Door handle locking failure
Af 2015 O O - O - O Use of door stoppers on evacuation elevator lobby fire doors
Ff 2019 O - - - O - Glass fire doors and missing automatic closing devices
Af 2022 - - O - - - -
Of 2024 - - - - - - Tactile paving interference and door stopper installation
Of 2024 - - O - - O Deformation of refuge floor fire doors

*Office facility (OF), accommodation facility (AF), factory facility (FF)

Table 5.
Classification of Major Fire Door Maintenance Problems and Causes
Classification target Major issues Major types and causes
Stairwell fire doors Fire door deformation, permanently open conditions, and failure to close properly • Wedge installation
• Sagging and frame deformation of aging fire doors
• Failure to close properly due to deterioration of door handles
• Failure to close properly caused by reduced door closer tension
• Opening and closing failures and deformation of fire doors on the first and top floors caused by wind pressure
Evacuation elevator lobbies Problems related to lobby fire door performance, maintenance, and internal storage • Bicycles and other stored items identified in evacuation elevator lobbies
• Wedge installation and removal of automatic closing devices for the routine use of evacuation elevators
• Fire extinguishers most commonly used as wedges for lobby fire doors
• Fire door bottom interference caused by tactile paving for persons with visual impairments
• Fire door threshold deformation caused by carts used during freight, parcel delivery, and moving operations
Common corridors and stairwells Storage-related problems • Multiple stored items, such as bicycles, household goods, and parcel deliveries, identified in common corridors and stairwells of residential complex buildings
• Stored items identified in common spaces near restaurants and commercial facilities on lower floors
• Private use of common spaces for storage
• Reduced evacuation route width and obstruction of evacuation paths
Entrance (Access) fire doors Reduced fire door closing performance • Reduced automatic closing performance caused by the installation of door stoppers beneath entrance fire doors
• Cases of intentional fixing to maintain permanently open conditions
Refuge floors in high-rise buildings Refuge floor access and operational management problems • Absence of evacuation guidance maps on refuge floors
• Refuge floors used as storage rooms or rest areas
• Installation of electronic locking devices restricting access to refuge floors
• Automatic unlocking was possible during fire emergencies, but manual unlocking using buttons was not possible
Maintenance and inspection systems Exclusion from maintenance management and lack of awareness • Inspections focused primarily on the operation of detector-linked automatic closing devices
• Insufficient maintenance of permanently open or fixed-open fire doors
• Lack of awareness regarding the importance of fire compartmentation maintenance
• Insufficient awareness of the importance of maintaining fire compartmentation and fire doors

References

1. South China Morning Post (SCMP), "Government to Handle Wang Fuk Court Insurance Claims Under Buy-Back Plan: Hop On", https://www.scmp.com/news/hong-kong/society/article/3354276/government-handle-wang-fuk-court-insurance-claims-under-buyback-plan-administrator (2026).

2. Seo-gu, Incheon Metropolitan City, "2024 White Paper on the Electric Vehicle Fire in the Underground Parking Lot of Cheongna Apartment", Incheon, Korea (2024).

3. H. W. Seo, D. H. Kim and D. H. Choi, “A Study on Related Materials Analysis and Validation Tests for the Selection of Check Points at the Quality Management in Construction Sites-Focused on Fire Doors and Fire Shutters-”, Journal of the Korean Society of Hazard Mitigation, Vol. 16, No. 5, pp. 189-198 (2016), https://doi.org/10.9798/KOSHAM.2016.16.5.189.
crossref
4. M. O. Yoon, “A Study on Major Issues in Litigation on Fire Door Performance”, Fire Science and Engineering, Vol. 35, No. 1, pp. 137-142 (2021), https://doi.org/10.7731/KIFSE.265d7867.
crossref
5. H. Y. Shim and W. J. Park, “Statistical Analysis of the Structure and Performance of Fire Doors for Evacuation Space and Common Areas in Apartment Housing”, Journal of the Korea Institute of Building Construction, Vol. 22, No. 3, pp. 239-249 (2022), https://doi.org/10.5345/JKIBC.2022.22.3.239.
crossref
6. Y. S. Kim, Y. L. Lee, Y. H. Son and Y. J. Kwon, “Optimizing Maintenance Strategies for Public Fire Doors in Apartment Buildings: Study on Deterioration Patterns and Replacement Timing”, Journal of the Korean Society of Hazard Mitigation, Vol. 24, No. 3, pp. 115-121 (2024), https://doi.org/10.9798/KOSHAM.2023.24.3.115.
crossref
7. S. H. Kim and J. Y. Lee, “Influence of Spatial, Environmental, and Managerial Factors on Stairwell Fire Door Opening in Apartment Buildings”, Journal of the Society of Disaster Information, Vol. 21, No. 3, pp. 707-717 (2025), https://doi.org/10.15683/kosdi.2025.9.30.707.
crossref
8. K. S. Kim, “A Study on Analysis of Aging Degradation and Improvement of Maintenance System for Apartment Fire Doors”, Journal of the Regional Association of Architectural Institute of Korea, Vol. 28, No. 1, pp. 37-42 (2026).

9. Korean Agency for Technology and Standards (KATS), "KS F 2268-1: Fire Resistance Tests for Door Assemblies" (2021).

10. Korean Agency for Technology and Standards (KATS), "KS F 2846: Methods for Measuring Smoke Penetration through Door Assemblies" (2013).

11. Ministry of Land, Infrastructure and Transport, "Building Act" (2025).

12. Ministry of Land, Infrastructure and Transport, "Enforcement Decree of the Building Act" (2025).

13. Ministry of Land, Infrastructure and Transport, "Rule on the Standards for Egress and Fire-Proof Structures of Buildings" (2025).

14. Ministry of the Interior and Safety, "Special Act on Management of Disasters in Super High-Rise Buildings and Complex Buildings With Underground Connections" (2025).

15. NFPC 501A, "National Fire Performance Code for Smoke Control Systems for Fire Escape Stairwells and Ancillary Rooms", National Fire Agency (2025).

16. NFPA, "NFPA 80: Standard for Fire Doors and Other Opening Protectives, National Fire Protection Association", Quincy, MA, USA (2022).

17. NFPA, "NFPA 101: Life Safety Code, National Fire Protection Association, Quincy", MA, USA (2021).

18. International Code Council, "International Building Code (IBC)", Washington, DC, USA (2021).

19. J. H. Klote, J. A. Milke, P. G. Turnbull, A. Kashef and M. J. Ferreira, "Smoke Control Engineering Handbook", Society of Fire Protection Engineers (SFPE), Bethesda, MD, USA (2012).



ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next