1. Introduction
Recently, urban environments in the Republic of Korea have become increasingly dense and complex, leading to a rapid increase in the construction of high-rise and super high-rise buildings. In particular, super high-rise mixed-use buildings centered on commercial occupancies, such as office facilities, accommodation facilities, and officetels (mixed-use residential and office buildings), have become more common, along with building designs integrating large-scale underground parking areas and vertical evacuation routes. Although these high-rise buildings offer advantages in terms of land-use efficiency and space utilization, they also present challenges, including an increased potential for vertical smoke and heat spread and prolonged evacuation times during fire incidents. In particular, in buildings where underground parking lots, stairwells, and evacuation elevator lobbies are interconnected, smoke control and the protection of evacuation routes become critical safety considerations. In recent fire incidents involving apartment buildings and commercial facilities, evacuation difficulties caused by smoke spread have repeatedly emerged as more significant concerns than the fire itself. Representative domestic underground parking lot fire incidents have raised major concerns regarding large-scale smoke spread and occupant evacuation, whereas overseas incidents, such as the Tai Po Wang Fuk Court fire in Hong Kong, have highlighted concerns regarding the risk of fire spread associated with inadequate fire compartmentation and fire door management [
1,
2].
In high-rise building fires, fire doors are not merely access doors but essential fire safety and evacuation facilities that maintain fire compartmentation and prevent smoke spread. In particular, fire doors installed in ancillary rooms of special evacuation stairwells and evacuation elevator lobbies play an important role in preventing smoke infiltration into stairwells and protecting evacuation routes. However, during routine building operation, fire doors are often permanently left open, and door closers are frequently removed for user convenience, resulting in the loss of fire compartmentation performance. Current building regulations and fire safety codes specify standards for fire door construction, self-closing performance, and opening direction for evacuation; however, studies investigating their actual operational and maintenance status remain relatively limited. Previous studies have mainly focused on fire performance testing and regulatory analyses, whereas field investigations analyzing the operational conditions and maintenance problems of fire doors in high-rise buildings remain scarce [
3-
8].
Therefore, this study aims to investigate the operational status of fire doors in high-rise and super high-rise buildings, analyze maintenance problems and cases of fire compartmentation damage, and propose improvement measures to enhance evacuation safety. In addition, this study examines discrepancies between the current evacuation and fire protection systems and actual operational conditions.
2. Literature Review
2.1. Importance of fire doors
Fire doors are essential fire protection and evacuation facilities designed to maintain the integrity of fire compartmentation by preventing the spread of flames and smoke during fire incidents and securing evacuation time for occupants. In particular, in high-rise and super high-rise buildings, fire doors installed in ancillary rooms of special evacuation stairwells, evacuation elevator lobbies, and basement parking connections play important roles in preventing smoke spread and ensuring evacuation safety. To fulfill these functions, fire doors are required to provide adequate fire resistance and smoke leakage performance, which are verified through standardized testing methods and performance criteria [
9-
15]. In high-rise building fires, stairwells serve as the final evacuation route and become the primary spaces for the vertical evacuation of occupants during fire emergencies. Therefore, preventing smoke infiltration into stairwells and maintaining tenable evacuation conditions are critical. In particular, fire doors installed in ancillary rooms of special evacuation stairwells and evacuation elevator lobbies serve as key facilities for preventing smoke infiltration from fire compartments into stairwells. However, when fire doors are permanently left open or their self-closing functions are not properly maintained, the risk of smoke infiltration into stairwells increases significantly. In addition, open fire doors can adversely affect smoke control systems and differential pressure maintenance, potentially reducing the overall evacuation safety performance of high-rise buildings. Therefore, stairwell fire doors should not be regarded merely as access doors but as essential fire safety facilities for protecting evacuation routes, requiring continuous maintenance and proper closure at all times [
16-
19].
2.2. Legal framework for evacuation and fire protection in high-rise buildings
The legal framework governing evacuation and fire protection in high-rise buildings in the Republic of Korea is primarily composed of the Building Act, the Act on the Installation and Management of Firefighting Systems, and the Rule on the Standards for Egress and Fire-Proof Structures of Buildings. In particular, the Building Act stipulates architectural fire protection requirements for special evacuation staircases, evacuation elevators, fire compartmentation, and fire doors, whereas the Act on the Installation and Management of Firefighting Systems provides requirements for securing evacuation safety through smoke control systems, alarm systems, and fire extinguishing systems [
11-
15]. In high-rise and super high-rise buildings, the installation of special evacuation staircases and evacuation elevators is mandatory, and fire doors installed in stairwells and ancillary rooms are designated as essential facilities for preventing smoke spread during fire incidents. Major regulations related to fire doors include Article 49 of the Building Act concerning evacuation facilities and occupancy restrictions; Article 48 of the Enforcement Decree of the Building Act concerning installation standards for stairways, corridors, and exits; Article 64 of the Enforcement Decree of the Building Act concerning the classification of fire doors; Article 9 of the Rule on the Standards for Egress and Fire-Proof Structures of Buildings concerning the structure of evacuation staircases and special evacuation staircases; and Article 26 of the same Rule concerning fire door construction [
11-
13]. In addition, fire doors are required to maintain self-closing performance, the appropriate opening direction for evacuation, and smoke control performance while preserving fire compartmentation during fire incidents [
14-
18].
2.3. Review of previous studies
As shown in
Table 1, studies on the performance maintenance and management of fire doors have been conducted continuously in the Republic of Korea in recent years. Early studies mainly focused on the construction quality and fire performance of fire doors. Seo et al. [
3] analyzed pre-completion safety inspection records and fire performance test data and identified field quality control problems, such as missing door closers, excessive fire door gaps, and missing hardware components. In addition, Shim and Park [
5] conducted a statistical analysis of fire resistance test data for fire doors installed in evacuation spaces and common areas of apartment buildings and analyzed their structural characteristics and the major factors influencing fire door performance. Subsequent studies expanded their focus to the maintenance, durability, and management of fire doors. Yoon [
4] analyzed major litigation cases related to fire door performance and identified key issues concerning durability, maintenance responsibility, performance verification procedures, and the scope of defect repairs. The study emphasized the importance of periodic inspection and maintenance systems for ensuring long-term fire door performance. Kim et al. [
6] analyzed fire door operation probabilities and expert survey results and reported that fire doors older than 15 years exhibited increasing failure rates. The major deterioration factors included twisting, corrosion, dents, and physical damage. Recently, field investigations of actual operational conditions and occupant behavior have also increased. Kim and Lee [
7] conducted a checklist-based field investigation of stairwell fire doors in apartment buildings and reported that a significant proportion of abnormal fire door opening conditions resulted from intentional fixing. The study also indicated that the frequency of fire door opening and abnormal conditions increased with building age. In addition, the authors suggested that increased storage of items in surrounding areas could be associated with permanently open fire doors. In addition to field investigations of operational conditions, studies investigating the deterioration of actual fire resistance performance have also been conducted. Kim [
8] analyzed fire resistance test results for apartment fire doors and found that fire door performance failure rates tended to increase with building age.
However, most previous studies have been conducted on apartment buildings and have focused on residential entrance doors, common-area fire doors, and stairwell fire doors. In addition, previous studies have primarily addressed the fire resistance performance, structural characteristics, and aging-related problems of fire doors, whereas studies investigating the actual operational conditions and field maintenance status of fire doors in high-rise and super high-rise buildings remain relatively limited. In particular, studies investigating fire compartmentation maintenance problems in evacuation elevator lobbies, refuge floors, common corridors, and mixed-use buildings have been limited, and field investigations targeting high-rise and super high-rise buildings with mixed occupancies, such as commercial facilities, accommodation facilities, and office facilities, remain scarce.
3. Research Methodology and Surveyed Buildings
3.1. Scope of the study and investigation method
This study was conducted to investigate the operational status of fire doors and analyze related problems in high-rise and super high-rise buildings 30 stories or more. Rather than focusing on the structural fire performance of fire doors, this study primarily examined their actual operational conditions and maintenance status. The investigation focused primarily on the condition of fire doors in ancillary rooms of special evacuation stairwells, evacuation elevator lobbies, basement parking connections, and corridors. During the investigation, architectural drawings were first reviewed to identify the fire compartmentation layout and the installation locations of fire doors. Subsequently, on-site inspections were conducted to examine the maintenance status of the fire doors. In addition, operational testing was performed on selected fire doors to verify their self-closing performance and normal operation, and major deficiencies were documented through photographic records. As shown in
Table 2, the main investigation items included fire door closing conditions, maintenance of self-closing functions, maintenance of fire compartmentation, and management of evacuation routes. The investigation was not conducted as a comprehensive inspection of all floors in the surveyed buildings. Instead, a sampling-based investigation method was applied by dividing each building into lower, middle, and upper sections according to its height. However, when recurring problems, such as malfunctioning self-closing functions, permanently open fire doors, and damage to fire compartmentation, were identified during the investigation, the scope of the investigation was expanded to include multiple floors or nearly the entire building.
3.2. Overview of the investigated buildings
Table 3 presents an overview of the buildings investigated in this study. The survey targeted all high-rise and super high-rise buildings with 30 stories or more located in Haeundae-gu, Busan, Republic of Korea, and a full census survey was conducted for all buildings that met the selection criteria at the time of the investigation. The investigated buildings included office facilities, officetels, accommodation facilities, and a factory facility, and field investigations were conducted for a total of 33 buildings. In terms of occupancy type, the investigated buildings comprised 15 office facilities, 9 accommodation facilities, 8 officetels, and 1 factory facility. The approval years of the investigated buildings ranged from 2003 to 2024, and the building heights ranged from 30 to 94 stories. In addition, the floor area ratio ranged from approximately 457% to 1,321%, whereas the building coverage ratio ranged from approximately 13% to 80%.
Figure 1 illustrates the distribution of the investigated buildings according to elapsed years, number of stories, floor area ratio, and building coverage ratio. The investigation results showed that buildings with 30-39 stories accounted for the largest proportion of the surveyed buildings, whereas floor area ratios were most frequently distributed within the range of 800%-999%.
4. Results of Field Investigation
The field investigation results indicated that fire door maintenance problems in high-rise and super high-rise buildings could generally be classified into several categories, including permanently open fire doors, maintenance problems involving fire doors in evacuation elevator lobbies, storage-related misuse of common spaces, fire door deformation and failure to close properly, and limitations in maintenance and inspection systems.
Figure 2 presents representative examples of permanently open and intentionally fixed-open fire doors. The investigation repeatedly identified permanently open fire doors at first-floor entrances, basement parking connections, and evacuation elevator lobbies. In many cases, fire doors were intentionally fixed open using fire extinguishers, wedges, or door stoppers. In some buildings, fire doors were routinely kept in a permanently open condition, and these problems were associated with user convenience and freight movement activities, such as moving and delivery operations.
Figure 3 presents examples of fire door deformation and maintenance problems. Cases involving the removal of fire doors, fire door deformation, defective door handles, and malfunctioning door closers were identified in several buildings. In particular, older buildings exhibited relatively frequent problems, such as sagging fire doors, excessive gaps, and sealing failures. In addition, some fire doors failed to open or close properly because of wind pressure effects.
Figure 4 presents examples of storage-related obstructions in evacuation routes and common spaces. In residential complex buildings and officetels, bicycles, household goods, and parcel deliveries were frequently found in evacuation routes and common areas. In some buildings, portions of common corridors and evacuation spaces were effectively used as private storage areas. In addition, stored items in ancillary rooms of special evacuation stairwells and evacuation elevator lobbies reduced the effective width of evacuation routes and obstructed evacuation paths.
Table 4 summarizes representative cases that were repeatedly identified or considered relatively severe during the field investigation, whereas
Table 5 provides a comprehensive classification of the major problem types and their underlying causes based on the investigation findings. The investigation indicated that fire door maintenance problems were associated not only with occupant behavior but also with maintenance management systems and inspection practices. In particular, inspections frequently focused on the operational status of detector-linked automatic closing devices, whereas inspections of fire door deformation, permanently open conditions, and the maintenance of fire compartmentation were relatively insufficient.
5. Improvement Directions for Major Problems
Based on the major problems and underlying causes identified in
Tables 4 and
5, the following improvement measures are proposed to maintain fire compartmentation and enhance evacuation safety.
First, to address the problem of permanently open and fixed-open fire doors, the application of detector-linked automatic closing devices should be considered for fire doors installed in frequently used locations, such as basement parking connections, first-floor entrances, and evacuation elevator lobbies. In addition, because repeated instances were identified in which fire extinguishers installed in corridors and evacuation routes were used to hold fire doors open, the fixed installation methods for fire extinguishers should be reviewed, and management standards for the areas surrounding fire doors should be strengthened. Furthermore, the installation of information stickers and guidance notices on stairwell and evacuation elevator lobby fire doors should be reinforced to emphasize the prohibition of permanently open fire doors, the importance of maintaining fire doors, and restrictions on non-emergency use. Fire safety planning and fire door operation strategies should also take actual occupant behavior and building usage characteristics during normal operation into account.
Second, regarding maintenance problems involving fire doors in evacuation elevator lobbies, the investigation confirmed that these problems repeatedly occurred during the use of evacuation elevators for freight transport, moving activities, and parcel delivery. In particular, cases involving the removal of automatic closing devices and the intentional fixing of fire doors were identified, indicating the need for further review of maintenance standards and operational management measures for fire doors in evacuation elevator lobbies. In addition, further discussion is required regarding restrictions on the non-emergency use of evacuation elevators and the reinforcement of evacuation elevator lobby management.
Third, regarding storage-related obstructions identified in residential officetels and apartment buildings, enforcement against stored items in evacuation routes and stairwells should be strengthened, while management standards for common spaces should be improved. In particular, repeated cases involving bicycles, household goods, and parcel deliveries were identified, indicating the need to strengthen control over the use of common corridors and evacuation spaces as private storage areas. In addition, enhanced management and inspection of common spaces surrounding lower-floor commercial facilities are also necessary. In particular, management measures should also address stored items that contain combustible materials and potential ignition sources, such as electric mobility devices and lithium-ion battery-powered equipment.
Fourth, regarding fire door deformation and failure to close properly, future maintenance procedures should include inspections not only of the operation of automatic closing devices but also of fire door sagging, excessive gaps, sealing failures, and opening and closing failures caused by wind pressure. In particular, regular maintenance and performance inspections should be strengthened for older buildings and for fire doors installed on the first and top floors, which are directly exposed to outdoor conditions. For lower- and upper-floor areas that are significantly affected by wind pressure, both design considerations and maintenance management should be strengthened to prevent fire door deformation.
Fifth, regarding limitations in fire door maintenance systems and inspection practices, the investigation indicated that current maintenance and fire safety inspection procedures tend to focus primarily on the interlocking operation of automatic closing devices. Therefore, future maintenance procedures should expand inspection items to include fire door structural deformation, permanently open conditions, the maintenance of fire compartmentation, and the management of evacuation routes. In addition, fire door management education for fire safety managers and maintenance personnel should be strengthened, while occupant awareness of the importance of fire doors should also be improved. Furthermore, practical evacuation guidance on refuge floors, evacuation safety zones, and evacuation procedures should be provided continuously to occupants.
6. Conclusion
This study investigated the operational status and maintenance conditions of fire doors in 33 high-rise and super high-rise buildings exceeding 30 stories through field inspections, operational testing, and photographic documentation.
The investigation identified recurring problems, including permanently open fire doors, removal of automatic closing devices, fire door deformation, obstruction of evacuation routes by stored items, and inadequate maintenance practices. In particular, maintenance problems were repeatedly identified in evacuation elevator lobbies and ancillary rooms of special evacuation stairwells, whereas older buildings exhibited relatively frequent problems related to sagging, excessive gaps, and wind pressure effects.
The results also indicated that current maintenance and inspection systems tend to focus primarily on detector-linked automatic closing devices, whereas inspections of structural deformation, permanently open conditions, and the maintenance of fire compartmentation remain insufficient. Accordingly, this study proposed improvement measures, including expanding detector-linked automatic closing systems, strengthening evacuation route management, reinforcing fire door inspection requirements, and improving occupant awareness of fire compartmentation maintenance.
This study provides valuable field investigation findings and practical insights into maintenance problems related to fire door operation in actual high-rise and super high-rise buildings. However, quantitative performance evaluation and validation of the proposed improvement measures were not conducted. Therefore, further studies investigating smoke control performance, differential pressure maintenance, wind pressure effects, and improvements to maintenance systems are needed.