Kim, Jang, Nam, Jung, and Lee: Numerical Analysis of Radiative Heat-Flux Distribution on Adjacent Tank Surface Exposed to Pool Fires of Diesel, Gasoline, and Methanol Under Wind Conditions

Abstract

Radiative heat transfer from a pool fire is the primary mechanism driving the domino escalation of fires among storage tanks in petrochemical complexes. This study quantitatively evaluated radiative heat flux incident on the outer wall of an adjacent storage tank using the Fire Dynamics Simulator. An 18 m diameter pool fire was analyzed for nine cases combining three fuels (diesel, gasoline, and methanol) and three wind speeds (0, 2, and 5 m/s). The adjacent tank (18 m diameter, 15 m height)—located 9 m from the fire source—was instrumented with 855 heat flux gauges arranged at 1 m intervals over its entire surface. The model was validated against 1 m and 30/50 m pool-fire experiments, which reproduced a distance-attenuation trend with a mean absolute error of approximately 20%. Gasoline yielded the highest radiative heat flux while methanol yielded the lowest; under no-wind conditions, the frontal-average fluxes were 4.44, 3.60, and 0.59 kW/m2 for gasoline, diesel, and methanol, respectively, thus reflecting differences in soot-driven flame luminosity. Increasing wind speed tilted the flame toward the tank and increased the frontal heat flux, with the greatest increase occurring between 0 and 2 m/s. Whereas whole-area and frontal averages remained below the 20 kW/m2 safety criterion for all cases, the local maximum for gasoline at 5 m/s reached 64.96 kW/m2—approximately 3.2 times the limit—and diesel exceeded the criterion as well. The flux peaked at the upper tank wall and at the front-facing point (φ = 0°) but decreased to almost zero on the rear due to self-shadowing. These results indicate that average-based assessments may overlook localized high-flux zones, which should be considered in domino-fire risk evaluation and tank-spacing design.

1. Introduction

Hazardous-material storage tanks in petrochemical complexes are used to store and manage large quantities of flammable liquids. A major risk is the domino effect, in which a pool fire originating from one tank propagates to adjacent tanks through radiative heat transfer, thus resulting in large-scale industrial accidents [1,2]. The escalation of fire-induced domino effects and the probability of tank damage are primarily governed by the magnitude and duration of radiative heat flux received by adjacent facilities. Such thermal exposure can increase the temperature of the tank steel, reduce its mechanical strength, and ultimately result in structural failure [2,3]. Conventional methods for predicting radiative heat flux from pool fires include semi-empirical approaches combining point-source or solid-flame models with configuration factors [4-6]. However, because these models represent flame using simplified geometric shapes, they cannot adequately account for actual flame behavior—such as flame tilt and soot shielding—or the spatial distribution of heat flux over different locations on the tank surface. Moreover the predicted values can vary considerably depending on the method used to calculate the configuration factor [6].
Radiative heat flux transferred from a pool fire to surrounding facilities is governed not only by the combustion heat and radiative fraction of fuel but also by flame geometry, including flame height, length, width, and tilt angle. Flame height and length determine the size and position of the effective radiating surface observed from the receiving surface, whereas flame width directly affects the radiating area exposed to the tank surface and the circumferential distribution of radiative heat flux. In general, flame geometry is governed by the pool diameter, heat-release rate, mass burning rate, and ambient wind speed. Under no-wind conditions, flame develops predominantly in the vertical direction due to buoyancy, whereas under windy conditions, it tilts downstream, thus altering its length and width as well as the relative position between the flame surface and receiving surface. Consequently, the radiative heat flux incident on the tank surface can vary substantially depending on the flame geometry and the resulting configuration factor between the flame and receiving surface, even for fires with the same total heat-release rate. Therefore, fire-risk assessment of storage tanks should consider not only the heat-release rate and radiative fraction but also wind-induced changes in flame geometry and the spatial distribution of heat flux over the tank surface. To overcome the limitations of conventional approaches, computational fluid dynamics-based analyses using the Fire Dynamics Simulator (FDS) have been extensively applied recently; furthermore, their applicability to large-scale crude-oil and ethanol pool fires as well as storage-terminal fire scenarios has been demonstrated [7,8].
The radiative characteristics of pool fires vary considerably depending on the type of stored fuel. This is because the mass burning rate, combustion heat, and flame luminosity associated with soot formation differ among fuels [4,9]. Hydrocarbon fuels such as diesel and gasoline exhibit high radiative fractions owing to highly luminous flames accompanied by substantial soot production, whereas methanol burns with a blue flame that generates little soot and thus has a relatively low radiative contribution [4,10]. Additionally, because outdoor storage tanks are continuously exposed to wind, wind-induced flame tilts and burning-rate changes critically govern the heat flux received by tanks located downwind [11,12]. Therefore, radiative heat flux at different locations on a tank surface must be analyzed quantitively while considering both fuel type and wind speed.
In this study, simulations were performed using the FDS for nine cases involving an 18 m diameter pool fire, combining three fuels (diesel, gasoline, and methanol) with wind speeds of 0, 2, and 5 m/s. Measurement points were arranged at 1 m intervals over a height range of 1-15 m on the outer wall of an 18 m diameter storage tank adjacent to the fire source. Subsequently, the magnitude of heat flux on the tank surface and its spatial distributions in the vertical and circumferential directions were quantitatively compared and analyzed by fuel type and wind speed. Additionally, the reliability of the numerical model was evaluated via comparison with previously reported experimental results for hydrocarbon pool fires, including a 1 m diameter crude-oil pool fire and 30 and 50 m diameter kerosene pool fires.

2. Analysis Method

2.1. Numerical model and analysis target

Numerical simulations were performed using the FDS. Large eddy simulation was performed to solve the Navier-Stokes equations, and 500 radiation angles were applied based on a subsequent convergence study. The fire source was modeled as a circular pool fire with a diameter D of 18 m and a height of 15 m. Meanwhile, the outer wall of an adjacent storage tank—with a diameter of 18 m and a height of 15 m—was selected as the target surface for analysis. A total of 855 radiative heat-flux sensors were arranged in a grid pattern on the outer wall of the tank at 1 m intervals in both the vertical and circumferential directions to measure the heat-flux distribution over the entire surface, i.e., from the front facing the fire source to the rear. The adjacent tank was positioned 9 m from the outer wall of the fire-source tank based on the storage capacity of the diesel tank. The wind direction was set from the fire source toward the outer wall of the adjacent tank.

2.2. Combustion properties by fuel type and analysis conditions

Diesel, gasoline, and methanol were selected as fuel sources because they exhibit distinct combustion heat and radiative characteristics. The combustion properties of each fuel are presented in Table 1 [8,9,13-18], together with those of kerosene and crude oil for reference. For methanol, which generates almost no soot, the radiative fraction was fixed at 0.20, whereas the diameter-dependent correlation χr = 0.35⋅exp (−0.05 D) was applied to hydrocarbon fuels [13].

3. Model Validation

To reliability of the simulation performed in this study was validated via comparison with experimental measurements of radiative heat flux from pool fires. The input conditions for the validation analysis are presented in Table 2 [8,13,19-23].

3.1. 1 m pool fire

To simulate a 1 m diameter pool fire, the number of solid angles for radiation calculation was varied from 200 to 800, and the radiative heat fluxes at distances of 3, 5, and 7 m from the center of the fire were compared with the experimental values. As shown in Figure 1, the heat-flux error decreased as the number of solid angles increased, and the results converged when the number of solid angles was 500 or greater. In the subsequent simulations, 500 solid angles were used to improve computational efficiency. At the near-field location (Length/Diameter, L/D = 3), the simulation results slightly overpredict the experimental value, whereas at the far-field location (L/D = 7), they underpredicted it; however, the mean absolute error over the entire range was approximately 20%, thus indicating acceptable agreement. Accordingly, 500 solid angles were adopted in the present analysis.

3.2. 30 and 50 m pool fires

In 1981, large-scale kerosene pool-fire experiments were conducted in Japan using tanks with diameters of 30 and 50 m. The water depth was approximately 200 mm, with an approximately 20 mm layer of kerosene placed above it, and radiative heat flux was measured at a height of 0.45 m above ground level at L/D = 1, 2, 3, 4, and 5 from the center of each pool fire. To evaluate the applicability of the model, the radiative heat fluxes at different distances from the 30 and 50 m pool fires were compared with the experimental values, as shown in Figures 2 and 3. In both cases, the heat flux decreased significantly with increasing distance from the fire source, thus exhibiting a clear distance-attenuation trend. However, at the location closest to the fire source (L/D = 1), the simulation overpredicted the experimental values, with errors of +61% and +105% for the 30 and 50 m pool fires, respectively, whereas the errors decreased to ±35% at the intermediate and far-field locations. The trend exhibited is similar to those reported in previous simulation studies. Because the model reproduced the overall attenuation trend with distance, it was considered suitable for relative comparisons of heat-flux distributions over the tank surface.

4. Results

4.1. Radiative heat flux on tank surface

Table 3 and Figure 4 present the time-averaged radiative heat flux calculated at each measurement point over the final 50 s after steady state was reached for the nine simulation conditions. Using the time-averaged value at each point, the mean over all measurement points, the mean over the frontal measurement points facing the fire source (|φ| < 30°), the 95th percentile of the spatial distribution, and the local maximum were calculated.
The mean over all measurement points, which was calculated as the arithmetic mean of the time-averaged radiative heat fluxes at all measurement points distributed over the tank surface, represents the overall level of radiative heat exposure received by the tank. The frontal mean represents the average thermal exposure in the region facing the fire source. Notably, these mean values may dilute high heat fluxes occurring at limited locations. By contrast, the local maximum is the highest time-averaged value among all measurement points and is thus sensitive to the result at a single point. Accordingly, this study utilized the 95th percentile of the spatial distribution to evaluate the upper range of heat flux across the tank surface while minimizing the effect of single-location extreme values.
Each evaluation metric showed distinct differences depending on fuel type and wind speed. Among the fuels, gasoline exhibited the highest values for all metrics, followed by diesel, while methanol showed substantially lower values. Under no-wind conditions, the frontal means for gasoline, diesel, and methanol were 4.44, 3.60, and 0.59 kW/m2, respectively. The frontal mean for methanol was approximately one-sixth to one-eighth of those for diesel and gasoline. This is because methanol generates almost no soot during combustion, whereas diesel and gasoline form soot-laden luminous flames, thus resulting in relatively greater radiative heat transfer.
As wind speed increased, the flame tilted toward the tank, thereby increasing the radiative heat flux over the frontal region facing the fire source. The increase in frontal mean was particularly pronounced when the wind speed increased from 0 to 2 m/s, with diesel and gasoline showing increases of approximately 2.6 and 2.9 times, respectively. When the wind speed increased from 2 to 5 m/s, the frontal mean for gasoline increased from 12.69 to 15.26 kW/m2, whereas that for diesel increased from 9.44 to 10.29 kW/m2—a reduced rate of increase. The frontal mean for methanol changed minimally with wind speed, with the value at 5 m/s lower than that at 2 m/s. This is attributed to the low radiative heat flux from methanol; consequently, wind-induced changes in flame geometry did not increase radiative exposure on the tank surface.
Appendix 6 of the Enforcement Rule of the Act on the Safety Control of Hazardous Substances stipulates that if the required clearance of an outdoor storage tank is reduced via a water spray system, then protective measures must be applied to any adjacent tank surface exposed to a radiative heat flux of 20 kW/m2 or greater from a fire. Accordingly, 20 kW/m2 was used as a reference value in this study to assess the necessity for water spray protection on the surface of an adjacent tank.
The mean over all measurement points and the frontal mean remained below 20 kW/m2 under all simulation conditions. However, under the gasoline 5 m/s condition, the 95th percentile was 19.87 kW/m2, which was close to the reference value, whereas the local maximum reached 64.96 kW/m2—approximately 3.2 times the reference value. Additionally, the local maximum values under the gasoline 2 m/s condition and the diesel 2 and 5 m/s conditions were 55.30, 50.71, and 49.57 kW/m2, respectively, which exceeded 20 kW/m2. This indicates that the mean over the entire surface or frontal region alone may not adequately represent the high radiative heat exposure concentrated at specific locations due to flame tilt and proximity to the flame. By contrast, the local maximum for methanol remained at or below 4.80 kW/m2 under all conditions.

4.2. Spatial distribution of heat flux on tank surface

Figure 5(a) shows the vertical distribution of incident radiative heat flux along the wall height at the frontal region of the tank facing the fire source (φ ≈ 0°). Along the frontal vertical line, the radiative heat flux increased with height, with maximum values concentrated in the upper region of the tank. This is attributed to the flame tilting toward the tank under downwind conditions and the flame base shifting downstream, thereby increasing the effective configuration factor between the flame surface and tank upper wall. In particular, because calculating the radiation from a tilted flame requires a configuration factor different from that for a vertical flame, the asymmetric distribution in the vertical direction observed in the present results is likely associated with wind-induced changes in flame geometry. However, the increase in heat flux with wind speed varied by fuel type and location, which is attributable to the combined effects of differences in radiative characteristics and flame structure among the fuels.
Gasoline exhibited the highest heat-flux values throughout the entire range, followed by diesel, whereas methanol exhibited extremely low values of 0-2 kW/m2 regardless of wind speed or height. Under the most severe condition of gasoline at 5 m/s, a localized region of high radiative heat flux reaching approximately 30 kW/m2 was formed near the upper section of the tank (z ≈ 15 m). These differences among the fuels are attributable to differences in soot formation. Hydrocarbon fuels such as diesel and gasoline generate substantial amounts of soot during combustion, thereby generating highly luminous flames and enhancing radiative heat transfer [4], whereas methanol exhibits clean-burning characteristics. Methanol fires exhibit distinctive behavior characterized by negligible to no carbonaceous soot formation. Consequently, the radiative fraction of methanol pool fires is reportedly the lowest among the fuels examined under identical conditions [23]. This is quantitatively consistent with the present results, in which the radiative heat flux of methanol is only a fraction of those of diesel and gasoline.
Figure 5(b) shows the circumferential distribution of radiative heat flux at the upper section of the tank (z = 15 m), where the maximum radiative heat flux was recorded, with the frontal point facing the fire source (φ = 0°) set as the reference. Under all fuel and wind-speed conditions, the radiative heat flux reached its maximum near φ = 0° and formed an approximately symmetric bell-shaped distribution about φ = 0°. This is because the point at φ = 0° directly faces the flame, thus resulting in the largest configuration factor between the flame surface and tank wall. By contrast, as |φ| increased, the angle between the tank-surface normal and the direction toward the flame increased, thereby decreasing both the effective configuration factor and radiative heat flux. In particular, the heat flux decreased significantly beyond |φ| = 60° and approached approximately zero on the rear side of the tank (|φ| > 90°). This is attributed to the fact that the rear side is located within a self-shadowed region owing to the tank curvature. These results are consistent with the basic assumptions of the solid flame model, in which a flame is idealized as a visible radiating body with a uniform surface emissive power and its radiative heat flux is calculated based on its position and configuration factor relative to the target surface [4,24]. In other words, the radiative hazard is concentrated within ±60° of the frontal region facing the fire source, thus quantitatively demonstrating the shielding effect of the tank shell on the rear side.

5. Conclusions

In this study, simulations were performed using the FDS for nine cases combining three fuels—diesel, gasoline, and methanol—with wind speeds of 0, 2, and 5 m/s for an 18 m diameter pool fire. Additionally, the magnitude and spatial distribution of radiative heat flux incident on the outer wall of an adjacent storage tank located 9 m from the fire source were quantitatively analyzed. The main findings are summarized as follows:
(1) For all evaluation metrics, gasoline exhibited the highest radiative heat flux, followed by diesel, whereas methanol showed substantially lower values. Based on the frontal mean under no-wind conditions, the heat-flux values for gasoline, diesel, and methanol were 4.44, 3.60, and 0.59 kW/m2, respectively. The value for methanol was approximately one-sixth to one-eighth of those for gasoline and diesel.
(2) As wind speed increased, the flame tilted toward the tank, thereby increasing the frontal radiative heat flux. The greatest increase was observed between the no-wind and 2 m/s conditions (approximately 2.6 and 2.9 times for diesel and for gasoline, respectively). Between 2 and 5 m/s, the frontal radiative heat flux for gasoline continued to increase, whereas the rate of increase for diesel decreased and the effect of flame tilt on methanol was limited because of its low absolute level of radiative heat flux.
(3) Under the gasoline 5 m/s condition, the 95th percentile was 19.87 kW/m2, which was close to the reference value, while the local maximum reached 64.96 kW/m2—approximately 3.2 times the reference value. For diesel, the local maximum values were 50.71 and 49.57 kW/m2 at 2 and 5 m/s, respectively, both of which exceeded the reference value. In regions of direct flame contact or close proximity to the tank surface, the heat flux may temporarily exceed the reference value significantly. By contrast, the local maximum for methanol was 4.80 kW/m2 and remained below the reference value under all conditions.
(4) In terms of spatial distribution, the radiative heat flux along the frontal vertical line increased with height and reached its maximum near the upper section of the tank (z ≈ 15 m). This is attributable to an increase in the effective configuration factor between the flame surface and tank upper wall as the flame tilts under downwind conditions. In the circumferential direction, the radiative heat flux exhibited a bell-shaped distribution with a maximum near φ = 0°—where the tank directly faces the fire source—and decreased rapidly with increasing |φ|, approaching approximately zero on the rear side of the tank (|φ| > 90°) due to self-shadowing.
In conclusion, the radiative heat flux received by an adjacent storage tank is critically governed by the soot formation and radiative characteristics of the fuel as well as by wind-induced flame tilt. Therefore, both the local-maximum heat flux and its spatial concentration should be considered when evaluating domino-fire risks and designing separation distances and protective measures for storage tanks in petrochemical complexes.

Notes

Author Contributions

For research articles with several authors, a short paragraph specifying their individual contributions must be provided. The following statements should be used "Conceptualization, W.K. and Y.J.; methodology, Y.J.; software, Y.J.; validation, Y.N., S.J. and W.K.; formal analysis, Y.J.; investigation, W.K.; resources, W.K.; data curation, W.K.; writing—original draft preparation, W.K.; writing—review and editing, W.K.; visualization, W.K.; supervision, W.K.; project administration, T.L.; funding acquisition, W.K. All authors have read and agreed to the published version of the manuscript."

Conflicts of Interest

The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported herein.

Acknowledgments

This study was supported by the National Research Foundation of Korea (NRF) grant funded by the Korean government (MSIT) (No. RS-2025-24523008).

Figure 1.
Comparison of radiative heat flux based on number of radiation angles for 1 m pool fire.
KIFSE-66f6e760f1.jpg
Figure 2.
30 m pool-fire heat flux.
KIFSE-66f6e760f2.jpg
Figure 3.
50 m pool-fire heat flux.
KIFSE-66f6e760f3.jpg
Figure 4.
Effect of wind speed on target tank heat flux for different fuel types.
KIFSE-66f6e760f4.jpg
Figure 5.
Spatial distribution of radiative heat flux on the target tank surface for different fuels and wind speeds.
KIFSE-66f6e760f5.jpg
Table 1.
Fuel Properties and Combustion Parameters
Fuel type Parameter
Formula Soot yield CO yield Heat of combustion (MJ/kg) Mass-loss rate Radiative fraction
Kerosene C12H26 0.042 [8] 0.017 [14] 43.2 [8] 0.063 [8] χr = 0.35⋅e^ (−0.05 D) [13]
Gasoline C8H18 0.038 [15] 0.015 [14] 44.5 [15] 0.077 [16]
Diesel C12H23 0.015 [15] 0.0067 [14] 44 [17] 0.054 [16]
Methanol CH3OH 0 [18] 0 [18] 19.9 [18] 0.017 [19] 0.20 [19]

Three wind-speed conditions, i.e., 0, 2, and 5 m/s, were considered. The heat flux on the tank surface was calculated for each case. The mean heat flux was obtained by time averaging the final 50 s interval under steady-state conditions.

Table 2.
Input Parameters for Each Simulation
Parameter 1 m pool fire [22] 30 and 50 m pool fires [23]
Pool diameter (m) 1 30 and 50 m
Fuel Arabian light crude oil Kerosene
Heat of combustion of fuel (kJ/kg) 43.2 (MJ/kg) [19] 43.2 (MJ/kg) [8]
Radiative fraction (χr) 0.33 [13] 0.08 (30 m), 0.03 (50 m) [13]
Soot yield (kg/kg) 0.08 [20] 0.42 [8]
Average mass burn rate (kg/m2⋅s) 0.0336 [21] 0.063 [8]
Domain size 16.8 × 16.8 × 19.6 320 × 320 × 150 (30 m), 550 × 50 × 150 (50 m)
x × y × z
Table 3.
Heat Flux by Wind Speed and Oil Type
Fuel Wind speed Whole-area average Frontal average (|φ| < 30°) 95th percentile Local maximum
Diesel 0 0.84 3.60 5.12 11.25
2 2.23 9.44 12.90 50.71
5 2.45 10.29 13.70 49.57
Gasoline 0 1.04 4.44 6.31 13.72
2 2.92 12.69 16.17 55.30
5 3.69 15.26 19.87 64.96
Methanol 0 0.14 0.59 0.92 2.66
2 0.21 0.97 1.36 4.80
5 0.16 0.75 1.04 4.80

References

1. I. Shaluf, N. Krir and S. Sakal, “Evaluation of the Domino Effect Caused by Pool Fires in a Tank Farm”, Journal of Pure & Applied Sciences, Vol. 23, No. 2, pp. 131-136 (2024), https://doi.org/10.51984/jopas.v23i2.2998.
crossref
2. V. Cozzani, G. Gubinelli and E. Salzano, “Escalation Thresholds in the Assessment of Domino Accidental Events”, Journal of Hazardous Materials, Vol. 129, No. 1-3, pp. 1-21 (2006).
crossref pmid
3. G. Landucci, G. Gubinelli, G. Antonioni and V. Cozzani, “The Assessment of the Damage Probability of Storage Tanks in Domino Events Triggered by Fire”, Accident Analysis & Prevention, Vol. 41, No. 6, pp. 1206-1215 (2009), https://doi.org/10.1016/j.aap.2008.05.006.
crossref
4. K. S. Mudan, “Thermal Radiation Hazards From Hydrocarbon Pool Fires”, Progress in Energy and Combustion Science, Vol. 10, No. 1, pp. 59-80 (1984), https://doi.org/10.1016/0360-1285(84)90119-9.
crossref
5. M. J. Hurley (Ed.), "SFPE Handbook of Fire Protection Engineering", 5th ed., Springer, New York (2016).

6. W. Wang, G. Tao and L. Zhang, “Comparative and Analysis Study of Pool Fire Radiant Heat Models Under Different View Factor Calculations”, Emergency Management Science and Technology, Vol. 4, e003. (2024), https://doi.org/10.48130/emst-0024-0005.
crossref
7. K. B. McGrattan, "Fire Dynamics Simulator (Version 4): Technical Reference Guide", NIST Special Publication (2006).

8. O. Ahmadi, S. B. Mortazavi, H. Pasdarshahri and H. A. Mohabadi, “Consequence Analysis of Large-Scale Pool Fire in Oil Storage Terminal Based on Computational Fluid Dynamic (CFD)”, Process Safety and Environmental Protection, Vol. 123, pp. 379-389 (2019), https://doi.org/10.1016/j.psep.2019.01.006.
crossref
9. V. Babrauskas, “Estimating Large Pool Fire Burning Rates”, Fire Technology, Vol. 19, pp. 251-261 (1983), https://doi.org/10.1007/BF02380810.
crossref
10. K. Sung, J. Chen, M. Bundy, M. Fernandez and A. Hamins, "The Thermal Character of a 1 m Methanol Pool Fire", NIST TN 2083, National Institute of Standards and Technology (2020). https://doi.org/10.6028/NIST.TN.2083.

11. C. Liu, Z. Yin, M. Jangi, X. Zhu, Y. Liu, R. Zhang, P. Huang and L. Yu, “Experimental Study on Radiative Heat Flux From Annular Pool Fires Under the Cross Airflow”, Applied Thermal Engineering, Vol. 260, pp. 124947(2025), https://doi.org/10.1016/j.applthermaleng.2024.124947.
crossref
12. F. D. S. Santos and A. Landesmann, “Thermal Performance-Based Analysis of Minimum Safe Distances Between Fuel Storage Tanks Exposed to Fire”, Fire Safety Journal, Vol. 69, pp. 57-68 (2014), https://doi.org/10.1016/j.firesaf.2014.08.010.
crossref
13. K. B. McGrattan, H. R. Baum and A. Hamins, "Thermal Radiation From Large Pool Fires", NIST IR 6546, National Institute of Standards and Technology (2000). https://doi.org/10.6028/NIST.IR.6546.

14. K. Biswas, "A Study of Radiation and Flow Properties of Buoyant Turbulent Diffusion Flames", Doctoral’s Thesis, Purdue University (2007).

15. J. R. Stewart, H. N. Phylaktou, G. E. Andrews and A. D. Burns, “Evaluation of CFD Simulations of Transient Pool Fire Burning Rates”, Journal of Loss Prevention in the Process Industries, Vol. 71, pp. 104495(2021), https://doi.org/10.1016/j.jlp.2021.104495.
crossref
16. J. M. Chatris, J. Quintela, J. Folch, E. Planas, J. Arnaldos and J. Casal, “Experimental Study of Burning Rate in Hydrocarbon Pool Fires”, Combustion and Flame, Vol. 126, No. 1-2, pp. 1373-1383 (2001).
crossref
17. J. Lei, W. Deng, Z. Liu, S. Mao, K. Saito, Y. Tao, H. Wu and C. Xie, “Experimental Study on Burning Rates of Large-Scale Hydrocarbon Pool Fires Under Controlled Wind Conditions”, Fire Safety Journal, Vol. 127, pp. 103517(2022), https://doi.org/10.1016/j.firesaf.2021.103517.
crossref
18. A. Tewarson, "Generation of Heat and Chemical Compounds in Fires, In: P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall, Jr. and J. M. Watts, Jr., (Eds.) SFPE Handbook of Fire Protection Engineering, 3rd ed.", National Fire Protection Association, Quincy, MA (2002).

19. P. V. Chulkov, “Numerical and Graphical Methods of Determining the Heat of Combustion of Oil Products”, Chemistry and Technology of Fuels and Oils, Vol. 4, pp. 68-70 (1968), https://doi.org/10.1007/BF00729566.
crossref
20. H. Koseki, “Large Scale Pool Fires: Results of Recent Experiments”, Fire Safety Science, Vol. 6, pp. 115-132 (2000), https://doi.org/10.3801/IAFSS.FSS.6-115.
crossref
21. H. Koseki, M. Kokkala and G. Mulholland, “Experimental Study of Boilover in Crude Oil Fires”, Fire Safety Science, Vol. 3, pp. 865-874 (1991), https://doi.org/10.3801/IAFSS.FSS.3-865.
crossref
22. T. Yamaguchi and K. Wakasa, “Oil Pool Fire Experiment”, Fire Safety Science, Vol. 1, pp. 911-918 (1986), https://doi.org/10.3801/IAFSS.FSS.1-911.
crossref
23. S. C. Kim, K. Y. Lee and A. Hamins, “Energy Balance in Medium-Scale Methanol, Ethanol, and Acetone Pool Fires”, Fire Safety Journal, Vol. 107, pp. 44-53 (2019), https://doi.org/10.1016/j.firesaf.2019.01.004.
crossref
24. M. Shokri and C. L. Beyler, “Radiation From Large Pool Fires”, Journal of Fire Protection Engineering, Vol. 1, No. 4, pp. 141-149 (1989), https://doi.org/10.1177/104239158900100404.
crossref
TOOLS
Share :
Facebook Twitter Linked In Google+ Line it
METRICS Graph View
  • 0 Crossref
  •    
  • 342 View
  • 15 Download
Related articles in Int J Fire Sci Eng.


ABOUT
BROWSE ARTICLES
EDITORIAL POLICY
AUTHOR INFORMATION
Editorial Office
Room 906, The Korea Science Technology Center The first building, 22, Teheran-ro 7 Gil, Gangnam-gu, Seoul, Republic of Korea
Tel: +82-2-555-2450/+82-2-555-2452    Fax: +82-2-3453-5855    E-mail: kifse@hanmail.net                

Copyright © 2026 by Korean Institute of Fire Science and Engineering.

Developed in M2PI

Close layer
prev next